Suitable Grids
Suitable Grids Inverters can be operated on the following grids:
-
208 V Delta - Corner Grounded, without neutral conductor
-
208 V Delta: 120 V WYE, with neutral conductor
-
220 V Delta - Corner Grounded, without neutral conductor
-
220 V Delta: 127 V WYE, with neutral conductor
-
240 V Delta - Corner Grounded, without neutral conductor
-
240 V: 120 V WYE, with neutral conductor
-
240 V: 120 V split phase, with neutral conductor
-
50 Hz (220 V Delta - Corner Grounded, 50 Hz, without neutral conductor)
-
50 HN (220 V Delta: 127 V WYE, 50 Hz, with neutral conductor)
240 V: 120 V Stinger Setup: 240N, HI1
Neutral conductor available
Setup 240 V: 120 V Split phase
(without neutral)
Setup: 240N, CAL1, HI1
(with neutral)
208 V Delta - Corner Grounded *
Setup: 208, CAL4, HI4
No neutral conductor
208 V Delta: 120 V WYE Setup: 208N, CAL2,
HI2
Neutral conductor available