TSt 5000 MV
Syn
3 x 208 / 230 / 400 / 460
V
AWG 6 *) 4G10
*) Canada / US cable type: Extra-hard usage
The item numbers of the different cables can be found in the Spare Parts List of
the device.
AWG ... American Wire Gauge
Connecting the
mains cable
If no mains cable is connected, a mains cable that is suitable for the connection
voltage must be fitted before commissioning.
The ground conductor should be approx. 10 - 15 mm (0.4 - 0.6 in.) longer than
the phase conductors.
An illustration of the mains cable connection can be found in the following sec-
tions: "Fitting the strain-relief device" or "Fitting the strain-relief device for
Canada / US". To connect the mains cable, proceed as follows:
1
Remove the side panel from the device
2
Push the mains cable in far enough to make it possible to connect the ground
conductor and the phase conductors to the block terminal properly.
3
Fit ferrules to the ground conductor and phase conductors
4
Connect the ground conductor and phase conductors to the block terminal
5
Use the strain-relief device to secure the mains cable
6
Fit the side panel of the device
Fitting the
Europe strain-
relief device
1
2
45
EN