AC input/output data
Max. output current 23.7 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Initial short circuit alternating cur-
rent / phase I
K
23.7 A
Total harmonic distortion < 2%
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal mains voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 5070 W (for 5 s)
Rated power 3680 W
Nominal output current 16 A
Nominal mains voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switching time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 97.6%
European efficiency (U
mpp nom
) 97.0%
European efficiency (U
mpp max
) 96.3%
European efficiency (U
mpp min
) 95.6%
Self-consumption at night 8.2 W
Cooling Controlled forced-air ventilation