CHAPTER 2 WIRING
Description of I/O Signals 2-89
2
CONT Through: Sequence Output Signal (Setting value 91 to 95)
This function allows communications input signals to be output via OUT signals of the hardware.
Function
The signals set to CONT 20 to 24 can be output through OUT signals 1 to 3 of the hardware. When
a CONT□ signal is allocated to an OUT signal, the ON/OFF status of the CONT signal is output
as a through signal to the OUT signal regardless of the function allocation of the corresponding
CONT signal.
CONT signals respectively correspond to CONT a to e
Corresponding CONT signals
CONTa CONT20
CONTb CONT21
CONTc CONT22
CONTd CONT23
CONTe CONT24
Parameter setting
Set the values (91 to 95) corresponds to the parameter of output terminal function setting. The
setting values to the relevant signals are as follows.
PA3_51 to 53
No. Name Setting range Change
51 OUT1 signal assignment
52 OUT2 signal assignment
53 OUT3 signal assignment
0 to 95 91 : CONTa through
92 : CONTb through
93 : CONTc through
94 : CONTd through
95 : CONTe through