65
3
Selection and application
3-6 Applications on the primary side of transformers
Table 3-15 Selecting MCCB for transformer primary circuit (Single-phase)
Single-phase, 400-440V/210-105V Transformers
Transformer capacity (kVA) 0.5 1.0 1.5 2.0 3.0 5.0
In: Rated primary current (rms A) 1.1 2.3 3.4 4.5 6.8 11.4
Irush: Exciting inrush current (rms A)
28.4 56.8 85.2 113.6 170.5 284.1
Short-circuit
current at 440V
1.5 (kA) BW32AAG–2P003 BW32AAG–2P010 BW32AAG–2P015 BW32SAT–2P015
2.5 (kA) BW32SAG–2P003 BW32RAG–2P010 BW32SAG–2P015 BW32SAT–2P015
7.5 (kA) BW50SAG–2P010 BW50SAG–2P015 BW50SAT–2P015
10 (kA) BW50RAG–2P015 BW50RAG–2P020 BW50RAG–2P030
18 (kA) BW125JAG–2P015
30 (kA) BW125JAG–2P015
36 (kA) BW125RAG–2P015
50 (kA) BW125RAG–2P015
65 (kA) BW50HAG-2P015
Transformer capacity (kVA) 7.5 10 15 20 30 50 75 100
In: Rated primary current (rms A) 17.0 22.7 34.1 45.5 68.2 113.6 170.5 227.3
Irush: Exciting inrush current (rms A)
426.1 568.2 852.3 1136.4 1704.5 2840.9 4261.4 5681.8
Short-circuit
current at 440V
1.5 (kA)
BW32SAT–2P030 BW50SAT–2P045 BW125JAT–2P060 BW125JAT–2P090 BW250EAT–2P175 BW400EAT–2P300 BW400EAT–2P400
2.5 (kA)
BW32SAT–2P030 BW50SAT–2P045 BW125JAT–2P060 BW125JAT–2P090 BW250EAT–2P175 BW400EAT–2P300 BW400EAT–2P400
7.5 ( kA)
BW50SAT–2P030 BW50SAT–2P045 BW125JAT–2P060 BW125JAT–2P090 BW250EAT–2P175 BW400EAT–2P300 BW400EAT–2P400
10 (kA)
BW50RAG–2P040 BW63RAG–2P060 BW125JAT–2P060 BW125JAT–2P090 BW250EAT–2P175 BW400EAT–2P300 BW400EAT–2P400
18 (kA)
BW125JAG–2P060 BW125JAT–2P060 BW125JAT–2P090 BW250EAT–2P175 BW400EAT–2P300 BW400EAT–2P400
30 (kA)
BW125JAG–2P060 BW125JAT–2P060 BW125JAT–2P090 BW250RAT–2P175 BW400EAT–2P300 BW400EAT–2P400
36 (kA)
BW125RAG–2P060 BW125RAG–2P075 BW125RAG–2P125 BW250RAT–2P125 BW250RAT–2P175 BW400RAT–2P300 BW400RAT–2P400
50 (kA)
BW125RAG–2P060 BW125RAG–2P075 BW125RAG–2P125 BW250RAT–2P125 BW250RAT–2P175 BW400RAT–2P300 BW400RAT–2P400
65 (kA)
BW125HAG–3P060 BW125HAG–2P075 BW125HAG–2P125 BW250HAG–2P150 BW400HAG–2P250 BW400HAG–2P400
−−
Note: A peak inrush current of 25 times the rated current is used in the calculations.
Single-phase, 200-220V/100-115V Transformers
Transformer capacity (kVA) 0.5 1.0 1.5 2.0 3.0 5.0
In: Rated primary current (rms A) 2.3 4.5 6.8 9.1 13.6 22.7
Irush: Exciting inrush current (rms A)
56.8 113.6 170.5 227.3 340.9 568.2
Short-circuit
current at 220V
2.5 (kA)
BW32AAG-2P010 BW32AAG-2P015 BW32SAT-2P015 BW32SAT-2P020 BW32SAT-2P030
5 (kA)
BW32SAG-2P010 BW32SAG-2P015 BW32SAT-2P015 BW32SAT-2P020 BW32SAT-2P030
10 (kA)
BW50SAG-2P010 BW50SAG-2P015 BW50SAT-2P015 BW50SAT-2P020 BW50SAT-2P030
25 (kA)
BW50RAG-2P010 BW50RAG-2P015 BW50RAG-2P020 BW50RAG-2P030 BW50RAG-2P040 BW63RAG-2P060
36 (kA)
BW125JAG-2P015 BW125JAG-2P075
50 (kA)
BW125JAG-2P015 BW125JAG-2P075
85 (kA)
BW125RAG-2P015 BW125RAG-2P075
100 (kA)
BW125RAG-2P015 BW125RAG-2P075
125 (kA)
BW50HAG-2P015 BW50HAG-2P075
Transformer capacity (kVA) 7.5 10 15 20 30 50 75 100
In: Rated primary current (rms A) 34.1 45.5 68.2 90.9 136.4 227.3 340.9 454.5
Irush: Exciting inrush current (rms A)
852.3 1136.4 1704.5 2272.7 3409.1 5681.8 8522.7 11363.6
Short-circuit
current at 220V
2.5 (kA)
BW50EAT-2P045
BW100EAT-2P075
BW125JAT-2P100
BW250EAT-2P150 BW250EAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
5 (kA)
BW50EAT-2P045
BW100EAT-2P075
BW125JAT-2P100
BW250EAT-2P150 BW250EAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
10 (kA)
BW50SAT-2P045
BW100EAT-2P075
BW125JAT-2P100
BW250EAT-2P150 BW250EAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
25 (kA)
BW100EAG-2P100
BW100EAT-2P075
BW125JAT-2P100
BW250EAT-2P150 BW250EAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
36 (kA)
BW125JAT-2P060 BW125JAT-2P075 BW125JAT-2P100
BW250EAT-2P150 BW250EAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
50 (kA)
BW125JAT-2P060 BW125JAT-2P075 BW125JAT-2P100
BW250RAT-2P150 BW250RAT-2P200 BW400EAT-2P400 BW630RAT-3P600
−
85 (kA)
BW125RAG-2P125 BW250RAG-2P150
BW250RAG-2P225
BW250RAT-2P150 BW250RAT-2P200 BW400RAT-2P400 BW630RAT-3P600
−
100 (kA)
BW125RAG-2P125 BW250RAG-2P150
BW250RAG-2P225
BW250RAT-2P150 BW250RAT-2P200 BW400RAT-2P400 BW630RAT-3P600
−
125 (kA)
BW125HAG-2P125
BW250HAG-2P150 BW250HAG-2P225
BW400HAG-2P300 BW630HAG-3P500
−−
−
Note: A peak inrush current of 25 times the rated current is used in the calculations.