Features
• An auxiliary contact can be added just by a single press.
• An auxiliary contact can be added to the front mounting unit
without changing the mounting area. This is conducive to the
miniaturization of the control panel.
• Using bifurcated contacts with high reliability of contact so
that it can operate normally with minimum operating voltage
and current (DC5V, 3mA) (SZ1FA11, SZ-A-C, SZ-AS1-C )
Ordering information (Types)
z Auxiliary contact unit
Types, applicable types
Descriptions (IEC, GB Description standard)
SZ-AS1-C
SZ1FA11
SZ-A22 - C
(1) Type
Product name
Auxiliary contact unit (Bifurcated-contact, compact)
Auxiliary contact unit (Single-contact, compact)
Auxiliary contact unit
(Bifurcated contact)
Auxiliary contact unit
(Single-contact)
Auxiliary contact unit
(Bifurcated contact)
Auxiliary contact unit
(Bifurcated contact)
No. of contacts
2
2
4
2
4
4
2
2
Contact arrangement
1NO1NC
1NO1NC
4NO
3NO1NC
2NO2NC
1NO3NC
4NC
2NO
1NO1NC
2NC
4NO
3NO1NC
2NO2NC
1NO3NC
4NC
2NO
1NO1NC
2NC
4NO
3NO1NC
2NO2NC
2NO
1NO1NC
2NC
1NO1NC
Mounting method:
Front mounting
Front mounting
Front mounting
Side mounting
Type (1)
SZ1FA11
SZ1FA11H
SZ1KA40
SZ1KA31
SZ1KA22
SZ1KA13
SZ1KA04
SZ1KA20
SZ1KA11
SZ1KA02
SZ1KA40H
SZ1KA31H
SZ1KA22H
SZ1KA13H
SZ1KA04H
SZ1KA20H
SZ1KA11H
SZ1KA02H
SZ-A40-C
SZ-A31-C
SZ-A22-C
SZ-A20-C
SZ-A11-C
SZ-A02-C
SZ-AS1-C
Applicable types
FJ-B06,B09,B12
FJ-B06/G,B09/G,B12/G
SKH4AB, SKH4GB
FJ-B18,B25,B32,B40,B50,
B65,B80,B95
FJ-B18/G,B25/G,B32/G
Note:
The units for front mounting and side
mounting should not be used
simultaneously
Type
Auxiliary contact
ratings
Rated insulation voltage
Ui [V]
Rated impulse voltage
Uimp [kV]
Conventional free air thermal current (Rated continuous current) [A]
Rated operatinal current
Ie
(A)
AC
(
AC-15)
AC
(
AC-12)
DC
(
DC-13)
*2
DC
(
DC-12)
SZ1FA11, SZ1KA□
690
6
10
3
3
1
0.5
6
6
6
3
2
1
0.3
0.2
3
2
1.5
0.5
DC5V,3mA
SZ-A
□-C, SZ-AS1-C
690
6
10
6
3
1.5
1.2
10
8
5
5
3
1.5
0.55
0.27
5
3
2.5
1
DC5V,3mA
110V
220/230V
380/400V
500/600V
110V
220/230V
380/400V
500/600V
24V
48V
110V
220V
24V
48V
110V
220V
Minimum operating voltage, current *1
SZ1FA11H, SZ1KA□H
690
6
10
6
3
1.5
1.2
10
10
10
5
4
1
0.5
0.25
8
3.5
2.5
0.8
DC24V,10mA
*
1
The failure level is 10
-7
for a normal environment without dust, dirt, or corrosive gas.
*
2
Time constant L/R=70ms
Auxiliary contact units
Information subject to change without notice