INF-TN1FSC-E 95
(1) Select “ANALOG INPUT/OUTPUT” on the “SYS-
TEM SETUP” screen.
Press the
ENT
key to display the ANALOG INPUT/
OUTPUT screen.
10.3.2 “ANALOG INPUT/OUTPUT”: when performing analog input/output
and calibration
This function allows you to set the analog input/output and perform input/output calibration.
AIch2
AO
AIch1
Red
(+)
Red
(+)
Black
(−)
Black
(−)
4 to 20mA
AO
(Output)
Indicator,
recorder,
regulator, etc.
(Note) The connector should
be connected to AI/AO.
Analog output: 4 to 20mA DC 1 point “Load resistance under 600Ω”
Analog input: 4 to 20mA DC 1 point “Input resistance 200Ω”
4 to 20mA DC 1 point “Input resistance 200Ω” or
1 to 5V DC 1 point
Analog input/output cord (page 20)
−
+
AI
(Input)