EasyManua.ls Logo

Fuji Electric FLD-1 - Page 108

Fuji Electric FLD-1
189 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INF-TN1FSC-E 99
Current Input Caribration procedure
ENT
Input 4mA from external. Under calibration of 4mA
ENT
ENT
Input 20mA from external. Under calibration of 20mA End of calibration
After calibration, the “End of
Calibration” message appears
under the calibration button.
Analog input has already been calibrated on the factory setting
When you interrupt the calibration in the middle, the calibration value will be
lost.If you interrupt the calibration, start from the beginning again.
Calibrated analog inout required for AI measurement.
CAUTION

Table of Contents

Related product manuals