100 INF-TN1FSC-E
(4) “Input CH1 Voltage Input CALIBRATION”:
when adjusting zero and span for input signals
[Using a voltage generator]
Calibration procedure
1) 10.3.2(1) set the “ANALOG INPUT/OUTPUT” to the “USE”
2) 10.3.2(2) set the de nition of “SETTING” input CH to “VOLTAGE INPUT”.
[Operation]
(1) Move the cursor to the “INPUT” on the SETTING
screen by pressing the
or key and display the
INPUT screen.
Press the
ENT
key, and the cursor moves to “CH1:
INPUT CALIBRATION”.
Select “CH1: INPUT CALIBRATION.” by the
or
key and press the
ENT
key.
Select the kind of input you set on the “SETTING”
screen by the
or key and press the
ENT
key.
The cursor moves to “ADJUST”. Press the
ENT
key,
and you are ready to 1V calibration.
(2) Input 1V from external source . Then press the
ENT
key to adjust zero.
Follow the procedures described in next page of input
calibration.
(3) After input calibration of 1V is completed, 5V cali-
bration will be ready.
(4) Input 5V from external source. Then press the
ENT
key to adjust span.
Follow the procedures described in next page of input
calibration.