48 INF-TN1FSC-E
8.5.2 How to connect medium size sensor for FLD410 type only
(1) Remove the sensor cover.
Cover
(2) Mount the sensors so that the upstream and
downstream sensors can be distinguished from
each other.
Remove the cable clamp.
Note) In case of removing the cable clamp, be
sure not to lose the nut.
Driver
Cable
clamp
Cable
clamp
Nut
(3) Insert the coaxial cable through the cable lead-in
port.
loosen the terminal screws (G, +).
Connect core line white to (+), shield wire to
(G).
Note) At this time, remove the resistor.
Coaxial cable
CAUTION
Be careful not to cut your hands or etc. by
the cover.
CAUTION
For connecting coaxial cable to terminal,
turn the power off,.