5.2 Function Codes Table
5-14
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
C41
Analog input adjustment
(Terminal [C1] (V2 function))
(Offset)
-5.0 to 5.0%
Y*
Y
0.0
Y
Y
Y
Y
Y
C42
(Gain)
0.00 to 200.00%
Y*
Y
100.0
Y
Y
Y
Y
Y
C43
(Filter)
0.00 to 5.00 s
Y
Y
0.05
Y
Y
Y
Y
Y
C44
(Gain base point)
0.00 to 100.00%
Y*
Y
100.0
Y
Y
Y
Y
Y
C45
(Polarity selection)
0: Bipolar 1: Unipolar
N
Y
1
Y
Y
Y
Y
Y
C50
Bias (for frequency setting 1)
(Bias base point)
0.00 to 100.00%
Y*
Y
0.00
Y
Y
Y
N
Y
5-146
C53
Selection of normal/inverse
operation
(Frequency setting 1)
0: Normal 1: Inverse
Y
Y
0
Y
Y
Y
N
Y
5-146
C55
Analog input adjustment
(Terminal 12) (Bias)
-100.00 to 100.00%
Y
Y
0.00
Y
Y
Y
Y
Y
5-144
C56
(Bias base point)
0.00 to 100.00 %
Y
Y
0.00
Y
Y
Y
Y
Y
C58
(Display unit)
* Same as J105 (However, setting range is, 1 to 80)
Y
Y
2
Y
Y
Y
Y
Y
5-147
C59
(Maximum scale)
-999.00 to 0.00 to 9990.00
N
Y
100
Y
Y
Y
Y
Y
5-147
C60
(Minimum scale)
-999.00 to 0.00 to 9990.00
N
Y
0.00
Y
Y
Y
Y
Y
C61
Analog input adjustment
(Terminal[C1](C1 function))
(Bias)
-100.00 to 100.00 %
Y
Y
0.00
Y
Y
Y
Y
Y
5-144
C62
(Bias base point)
0.00 to 100.00 %
Y
Y
0.00
Y
Y
Y
Y
Y
C64
(Display unit)
* Same as J105 (However, setting range is, 1 to 80)
Y
Y
2
Y
Y
Y
Y
Y
5-147
C65
(Maximum scale)
-999.00 to 0.00 to 9990.00
N
Y
100
Y
Y
Y
Y
Y
5-147
C66
(Minimum scale)
-999.00 to 0.00 to 9990.00
N
Y
0.00
Y
Y
Y
Y
Y
C67
Analog input adjustment
(Terminal [C1] (V2 function))
(Bias)
-100.00 to 100.00 %
Y
Y
0.00
Y
Y
Y
Y
Y
5-144
C68
(Bias base point)
0.00 to 100.00 %
Y
Y
0.00
Y
Y
Y
Y
Y
C70
(Display unit)
* Same as J105 (However, setting range is,1 to 80)
Y
Y
2
Y
Y
Y
Y
Y
5-147
C71
(Maximum scale)
-999.00 to 0.00 to 9990.00
N
Y
100
Y
Y
Y
Y
Y
5-147
C72
(Minimum scale)
-999.00 to 0.00 to 9990.00
N
Y
0.00
Y
Y
Y
Y
Y
C89
Frequency correction 1 by
(Numerator)
-32768 to 32767 (Keypad display is 8000 to 7FFFH)
(Interpreted as 1 when the value is set to 0)
Y
Y
0001
Y
Y
Y
N
Y
C90
Frequency correction 2 by
(Denominator)
-32768 to 32767 (Keypad display is 8000 to 7FFFH)
(Interpreted as 1 when the value is set to 0)
Y
Y
0001
Y
Y
Y
N
Y

Table of Contents