5.2 Function Codes Table
5-18
Code Name Data setting range
Change when running
Data copying
Factory
Default
Initial capacitance of DC link
bus capacitor
For adjustment at replacement
(0000 to FFFF in hexadecimal)
capacitors on printed circuit
For adjustment at replacement
Change in cumulative motor run time (Reset is enabled)
Starting mode
(Auto search delay time 1)
Non-linear V/f 1 (Frequency)
0.0 (Cancel), 0.1 to 500.0 Hz
0 to 240 V:AVR operation ( 200 V class)
0 to 500V:AVR operation ( 400V class)
Non-linear V/f 2 (Frequency)
0.0 (Cancel), 0.1 to 500.0 Hz
0 to 240V:AVR operation ( 200V class)
0 to 500V:AVR operation ( 400V class)
Acceleration time (Jogging)
Deceleration time (Jogging)
Deceleration time for forced
stop
1st S-curve acceleration range
(At starting)
2nd S-curve acceleration
range (At arrival)
1st S-curve deceleration
range (At starting)
2nd S-curve deceleration
range (At arrival)
(Initial frequency setting)
0: Initial value is 0.00 Hz
1: Last UP/DOWN command value on releasing the run
Low limiter (Mode selection)
0: Limit by F16 (Frequency limiter: Low) and continue to
run
1: If the output frequency lowers below the one limited by
F16 (Frequency limiter: Low), decelerate to stop the
(Lower limiting frequency)
0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Non-linear V/f 3 (Frequency)
0.0 (Cancel), 0.1 to 500.0 Hz
0 to 240V: AVR operation ( 200V class)
0 to 500V: AVR operation ( 400V class)
Slip compensation 1
(Operating conditions
0: Enable during acceleration/deceleration, enable at
base frequency or higher
1: Disable during acceleration/deceleration, enable at
base frequency or higher
2: Enable during acceleration/deceleration, disable at
base frequency or higher
3: Disable during acceleration/deceleration, disable at
Anti-regenerative control
2: Torque limit control with force-to-stop
(Cancel limit control after three times of deceleration
time has passed)
3: DC link bus voltage control with force-to-stop
(Cancel voltage control after three times of deceleration
time has passed)
4: Torque limit control without force-to-stop
5: DC link bus voltage control without force-to-stop
Overload prevention control
0.00: Follow the deceleration time selected
0.01 to 100.00 Hz/s, 999 (Cancel)
Deceleration characteristics
(Available FRN0088E2
-2
/FRN0059E2
-4
or above)
Torque limiter *5
(Control target)
0: Torque limit
1: Torque current limit
(Frequency rising limiter
Service life of DC link bus
capacitor
0 to 8760 (in units of ten hours)
*5: Available at ROM version 0300 or later.
*10: 6.00s for inverters of nominal applied motor 22kW or below; 20.0s for those of 30kW or above.