5.3 Description of Function Codes
5-83
FUNCTION CODES
Chap 5
F31/F35
data
[FMA] output Data Definition of monitor amount 100%
17
Position error in
master-follower
operation
Deviation in angle
0% to 50% to 100%,
representing a deviation of -180°
to 0° to +180° respectively
18
Inverter heat sink
temperature
Heat sink detection temperature of
inverter
200°C/100%
21 PG feedback value
Actual speed (When PG interface
option card is mounted, the speed is
always calculated and output
regardless of the control method.)
Maximum speed as 100%
111
Customizable logic
output signal 1
Enable only at analog output 100% / 100%
112
Customizable logic
output signal 2
Enable only at analog output 100% / 100%
113
Customizable logic
output signal 3
Enable only at analog output 100% / 100%
114
Customizable logic
output signal 4
Enable only at analog output 100% / 100%
115
Customizable logic
output signal 5
Enable only at analog output 100% / 100%
116
Customizable logic
output signal 6
Enable only at analog output 100% / 100%
117
Customizable logic
output signal 7
Enable only at analog output 100% / 100%
118
Customizable logic
output signal 8
Enable only at analog output 100% / 100%
119
Customizable logic
output signal 9
Enable only at analog output 100% / 100%
120
Customizable logic
output signal 10
Enable only at analog output 100% / 100%
If F31 = 16 (PID output), J01 = 3 (Dancer control), and J62 = 2 or 3 (Ratio compensation enabled), the
PID output is equivalent to the ratio against the primary reference frequency and may vary within 300%
of the frequency. The monitor displays the PID output in a converted absolute
value (%). To indicate the
value up to the full
-scale of 300%, set F30 data to 33” (%).
Pulse rate (F33)
F33 specifies the pulse rate at which the output of the monitored item selected reaches 100%, in accordance with
the modes of the pulse counter to be connected.
Data setting range: 25 to 32000 (pulse/s)
Pulse output waveform Pulse output circuit
10.5 to
12.5V
Instruments