EasyManua.ls Logo

Fuji Electric FRENIC-Ace series - Page 51

Fuji Electric FRENIC-Ace series
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2 Wiring
2-19
INSTALLATION AND WIRING
Chap 2
Table 2.2-9 Recommended Wire Sizes, conforming to low voltage directive in Europe (continued)
HND Mode, Conforming to low voltage directive in Europe
Power
System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
[L1/R, L2/S, L3/T]
Ground terminal
[
z
G]
Inverter
output
[U, V, W]
For DC
reactor
connection
[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without
DC reactor
With DC
reactor
Without
DC reactor
Three-phase 400 V
0.75
FRN0002E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.1
FRN0004E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.2
FRN0006E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.0
FRN0007E2■-4
*10
2.5
2.5
2.5
2.5
2.5
2.5
2.5
5.5
FRN0012E2■-4
*10
2.5
2.5
2.5
2.5
2.5
2.5
2.5
7.5
FRN0022E2■-4
2.5
4
2.5
4
2.5
2.5
2.5
11
FRN0029E2■-4
4
6
4
6
4
4
2.5
15
FRN0037E2■-4
6
10
6
16
6
6
2.5
18.5
FRN0044E2■-4
6
16
10
16
10
10
2.5
22
FRN0059E2■-4
10
16
10
16
10
16
2.5
30
FRN0072E2■-4
16
25
16
16
16
25
2.5
37
FRN0085E2■-4
25
35
16
16
25
25
-
45
FRN0105E2■-4
25
50
16
25
35
35
-
55
FRN0139E2■-4
35
70
16
35
50
50
-
75
FRN0168E2■-4
70
-
35
-
70
95
-
90
FRN0203E2■-4
95
-
50
-
95
120
-
110
FRN0240E2■-4
120
-
70
-
120
150
-
132
FRN0290E2■-4
150
-
95
-
150
95×2
-
160
FRN0361E2■-4
185
-
95
-
240
300
-
200
FRN0415E2■-4
300
-
150
-
300
150×2
-
220
FRN0520E2■-4
300
-
150
-
150×2
185×2
-
280
FRN0590E2■-4
185×2
-
185
-
240×2
300×2
-
HHD Mode, Conforming to low voltage directive in Europe
Power
System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
[L1/R, L2/S, L3/T]
Ground terminal
[
z
G]
Inverter
output
[U, V, W]
For DC
reactor
connection
[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without
DC reactor
With DC
reactor
Without
DC reactor
Three-phase 400 V
0.4
FRN0002E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.75
FRN0004E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
FRN0006E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.2
FRN0007E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.7
FRN0012E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
5.5
FRN0022E2■-4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
7.5
FRN0029E2■-4
2.5
4
2.5
4
2.5
2.5
2.5
11
FRN0037E2■-4
4
6
4
6
4
4
2.5
15
FRN0044E2■-4
6
10
6
10
6
6
2.5
18.5
FRN0059E2■-4
6
16
10
16
10
10
2.5
22
FRN0072E2■-4
10
16
10
16
10
16
2.5
30
FRN0085E2■-4
16
25
16
16
16
25
-
37
FRN0105E2■-4
25
35
16
16
25
25
-
45
FRN0139E2■-4
25
50
16
25
35
35
-
55
FRN0168E2■-4
35
70
16
35
50
50
-
75
FRN0203E2■-4
70
-
35
-
70
95
-
90
FRN0240E2■-4
95
-
50
-
95
120
-
110
FRN0290E2■-4
120
-
70
-
120
150
-
132
FRN0361E2■-4
150
-
95
-
150
185
-
160
FRN0415E2■-4
185
-
95
-
240
300
-
200
FRN0520E2■-4
300
-
150
-
300
150×2
-
220
FRN0590E2■-4
300
-
150
-
150×2
185×2
-
Single-phase
200V
0.1
FRN0001E2■-7
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.2
FRN0002E2■-7
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.4
FRN0003E2■-7
2.5
2.5
2.5
2.5
2.5
2.5
2.5
0.75
FRN0005E2■-7
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
FRN0008E2■-7
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.2
FRN0011E2■-7
2.5
4
2.5
4
2.5
2.5
2.5
The recommended wire sizes for the main circuit terminals assume using 70°C 600 V PVC wire at 40°C ambient
temperature.
*10 ND-spec.

Table of Contents

Related product manuals