2.2 Wiring
2-22
Table 2.2-12 Recommended wire sizes, Ambient temperature : Below 40°C, Wire type: 60°C wire (continued)
HHD Mode, Ambient temperature: Below 40°C, Wire type: 60°C wire
Power
System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
[L1/R, L2/S, L3/T]
Ground
terminal
[
z
G]
Inverter
output
[U, V, W]
For DC
reactor
connection
[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without DC
reactor
Three-phase 200 V
0.1
FRN0001E2■-2
2
2
2
2
2
2
0.2
FRN0002E2■-2
2
2
2
2
2
2
0.4
FRN0004E2■-2
2
2
2
2
2
2
0.75
FRN0006E2■-2
2
2
2
2
2
2
1.5
FRN0010E2■-2
2
2
2
2
2
2
2.2
FRN0012E2■-2
2
2
2
2
2
2
3.7
FRN0020E2■-2
2
3.5
2
2
2
2
5.5
FRN0030E2■-2
2
5.5
3.5
3.5
3.5
2
7.5
FRN0040E2■-2
3.5
8
5.5
5.5
5.5
2
11
FRN0056E2■-2
8
14
5.5
8
14
2
15
FRN0069E2■-2
14
22
5.5
14
14
2
18.5
FRN0088E2■-2
14
38
*7
8
22
22
2
22
FRN0115E2■-2
22
38
*7
8
22
38
*7
2
Three-phase 400 V
0.4
FRN0002E2■-4
2
2
2
2
2
2
0.75
FRN0004E2■-4
2
2
2
2
2
2
1.5
FRN0006E2■-4
2
2
2
2
2
2
2.2
FRN0007E2■-4
2
2
2
2
2
2
3.7
FRN0012E2■-4
2
2
2
2
2
2
5.5
FRN0022E2■-4
2
2
2
2
2
2
7.5
FRN0029E2■-4
2
3.5
2
2
2
2
11
FRN0037E2■-4
2
5.5
3.5
3.5
3.5
2
15
FRN0044E2■-4
3.5
8
5.5
3.5
5.5
2
18.5
FRN0059E2■-4
5.5
14
5.5
5.5
8
*1
2
22
FRN0072E2■-4
8
*1
14
5.5
8
*1
14
2
30
FRN0085E2■-4
14
22
8
14
14
-
37
FRN0105E2■-4
14
38
8
22
22
-
45
FRN0139E2■-4
22
38
8
22
38
-
55
FRN0168E2■-4
38
60
14
38
38
-
75
FRN0203E2■-4
60
-
14
60
60
-
90
FRN0240E2■-4
60
-
14
60
100
-
110
FRN0290E2■-4
100
-
22
100
-
-
132
FRN0361E2■-4
100
-
22
-
-
-
160
FRN0415E2■-4
-
-
22
-
-
-
200
FRN0520E2■-4
-
-
38
-
-
-
220
FRN0590E2■-4
-
-
38
-
-
-
Single-phase
200 V
0.1
FRN0001E2■-7
2
2
2
2
2
2
0.2
FRN0002E2■-7
2
2
2
2
2
2
0.4
FRN0003E2■-7
2
2
2
2
2
2
0.75
FRN0005E2■-7
2
2
2
2
2
2
1.5
FRN0008E2■-7
2
2
2
2
2
2
2.2
FRN0011E2■-7
2
3.5
2
2
2
2
The recommended wire sizes for the main circuit terminals assume using 60°C IV wire.
*1 For compatible crimped terminals, please use model 8-L6 by JST Mfg. Co., Ltd. or equivalent.

Table of Contents

Related product manuals