BUSY 0 0 RL ALM DEC ACC IL
bit 0 FWD : 1= normal rotating
bit 1 REV : 1= reverse rotating
bit 2 EXT : 1= DC braking or pre-exciting
bit 3 INT : 1= inverter shut off
bit 4 BRK : 1= braking
bit 5 NUV : 1= DC link established
bit 6 TL : 1= torque limiting
bit 7 VL : 1= voltage limiting
bit 8 IL : 1= current limiting
bit 9 ACC : 1= accelerating
bit 10 DEC : 1= decelerating
bit 11 ALM : 1= batch alarm
bit 12 RL : 1= valid communication
bit 15 BUSY : 1= function code writing
■ Function code S05 only for the inverter communication
Issue a frequency command expressed in 0.01 Hz basis. Setting range: -327.68 Hz to 327.67 Hz
■ Function code M09 only for the inverter communication
Displays the current output frequency expressed in 0.01 Hz. Output range: -327.68 Hz to 327.67 Hz