2.2 Wiring
2-29
INSTALLATION AND WIRING
Chap 2
4) Ambient temperature: Below 50°C, Wire type: 60°C wire
Table 2.2-19 Recommended Wire Sizes, Ambient temperature: Below 50°C, Wire type: 60°C wire
ND Mode, Ambient temperature: Below 50°C, Wire type: 60°C wire
Power System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
(Note 1) [L1/R, L2/S, L3/T]
Ground
terminal
(Note 1)
[
z
G]
Inverter
output
(Note 1)
[U, V, W]
For DC
reactor
connection
(Note 1)
[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without DC
reactor
Three-phase 400 V
0.75
FRN0002E2■-4
2
2
2
2
2
2
1.5
FRN0004E2■-4
2
2
2
2
2
2
2.2
FRN0006E2■-4
2
2
2
2
2
2
3.0
FRN0007E2■-4
2
2
2
2
2
2
5.5
FRN0012E2■-4
2
3.5
2
2
2
2
11
FRN0022E2■-4
3.5
5.5
3.5
3.5
3.5
2
15
FRN0029E2■-4
5.5
14
5.5
5.5
5.5
2
18.5
FRN0037E2■-4
8
14
5.5
8
5.5
2
22
FRN0044E2■-4
8
14
5.5
14
8
2
30
FRN0059E2■-4
14
22
8
*1
14
22
2
37
FRN0072E2■-4
22
38
8
*1
22
38
2
45
FRN0085E2■-4
38
38
8
38
38
-
55
FRN0105E2■-4
38
60
14
38
60
-
75
FRN0139E2■-4
60
-
14
60
100
*2
-
90
FRN0168E2■-4
100
*2
-
14
100
*2
100
*2
-
110
FRN0203E2■-4
100
-
22
100
-
-
132
FRN0240E2■-4
-
-
22
-
-
-
160
FRN0290E2■-4
-
-
22
-
-
-
200
FRN0361E2■-4
-
-
38
-
-
-
220
FRN0415E2■-4
-
-
38
-
-
-
280
FRN0520E2■-4
-
-
38
-
-
-
315
FRN0590E2■-4
-
-
60
-
-
-
HD Mode, Ambient temperature: Below 50°C, Wire type: 60°C wire
Power System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
(Note 1) [L1/R, L2/S, L3/T]
Ground
terminal
(Note 1)
[
z
G]
Inverter
output
(Note 1)
[U, V, W]
For DC
reactor
connection
(Note 1)
*[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without DC
reactor
Three-phase 400 V
0.75
FRN0002E2■-4
2
2
2
2
2
2
1.1
FRN0004E2■-4
2
2
2
2
2
2
2.2
FRN0006E2■-4
2
2
2
2
2
2
3.0
FRN0007E2■-4
2
2
2
2
2
2
5.5
FRN0012E2■-4
2
3.5
2
2
2
2
7.5
FRN0022E2■-4
2
3.5
2
2
2
2
11
FRN0029E2■-4
3.5
5.5
3.5
3.5
3.5
2
15
FRN0037E2■-4
5.5
14
5.5
5.5
5.5
2
18.5
FRN0044E2■-4
8
14
5.5
8
5.5
2
22
FRN0059E2■-4
8
*1
14
5.5
14
14
2
30
FRN0072E2■-4
14
22
8
*1
14
22
2
37
FRN0085E2■-4
22
38
8
22
38
-
45
FRN0105E2■-4
38
38
8
38
38
-
55
FRN0139E2■-4
38
60
14
38
60
-
75
FRN0168E2■-4
60
-
14
60
100
*2
-
90
FRN0203E2■-4
100
-
14
100
100
-
110
FRN0240E2■-4
100
-
22
100
-
-
132
FRN0290E2■-4
-
-
22
-
-
-
160
FRN0361E2■-4
-
-
22
-
-
-
200
FRN0415E2■-4
-
-
38
-
-
-
220
FRN0520E2■-4
-
-
38
-
-
-
250
FRN0590E2■-4
-
-
38
-
-
-
Note 1) The rated current must be reduced for operation (Rated current x 80%). Recommended wire sizes