EasyManua.ls Logo

Fuji Electric FRENIC-Ace series - Page 65

Fuji Electric FRENIC-Ace series
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2 Wiring
2-33
INSTALLATION AND WIRING
Chap 2
Table 2.2-23 Recommended Wire Sizes, Ambient temperature: Below 50°C, Wire type: 75°C wire (continued)
HND Mode, Ambient temperature: Below 50°C, Wire type: 75°C wire
Power
System
Std
Applicable
Motor
(kW)
Inverter type
Recommended wire size (mm
2
)
Main power supply input
[L1/R, L2/S, L3/T]
Ground
terminal
[
z
G]
Inverter
output
[U, V, W]
For DC
reactor
connection
[P1, P(+)]
For braking
resistor
connection
[P(+), DB]
With DC
reactor
Without DC
reactor
Three-phase 200 V
0.2
FRN0001E2■-2
2
2
2
2
2
2
0.4
FRN0002E2■-2
2
2
2
2
2
2
0.75
FRN0004E2■-2
2
2
2
2
2
2
1.1
FRN0006E2■-2
2
2
2
2
2
2
2.2
FRN0010E2■-2
2
2
2
2
2
2
3.0
FRN0012E2■-2
*10
2
2
2
2
2
2
5.5
FRN0020E2■-2
*10
2
3.5
3.5
2
3.5
2
7.5
FRN0030E2■-2
3.5
5.5
5.5
3.5
5.5
2
11
FRN0040E2■-2
5.5
14
5.5
5.5
8
2
15
FRN0056E2■-2
14
14
5.5
14
14
2
18.5
FRN0069E2■-2
14
22
8
14
22
2
22
FRN0088E2■-2
22
38
*7
8
22
22
2
30
FRN0115E2■-2
38
*7
60
*8
14
38
*7
38
*7
2
Three-phase 400 V
0.75
FRN0002E2■-4
2
2
2
2
2
2
1.1
FRN0004E2■-4
2
2
2
2
2
2
2.2
FRN0006E2■-4
2
2
2
2
2
2
3.0
FRN0007E2■-4
*10
2
2
2
2
2
2
5.5
FRN0012E2■-4
*10
2
2
2
2
2
2
7.5
FRN0022E2■-4
2
2
2
2
2
2
11
FRN0029E2■-4
2
3.5
3.5
2
3.5
2
15
FRN0037E2■-4
3.5
5.5
3.5
5.5
5.5
2
18.5
FRN0044E2■-4
5.5
8
5.5
5.5
5.5
2
22
FRN0059E2■-4
5.5
14
5.5
8
*1
8
*1
2
30
FRN0072E2■-4
14
14
8
*1
14
14
2
37
FRN0085E2■-4
14
22
8
14
22
-
45
FRN0105E2■-4
22
38
8
22
22
-
55
FRN0139E2■-4
22
38
14
38
38
-
75
FRN0168E2■-4
38
-
14
60
60
-
90
FRN0203E2■-4
60
-
14
60
100
-
110
FRN0240E2■-4
100
-
22
100
100
-
132
FRN0290E2■-4
100
-
22
100
150
*3
-
160
FRN0361E2■-4
150
-
22
150
150
-
200
FRN0415E2■-4
150
-
38
200
250
-
220
FRN0520E2■-4
200
-
38
200
250
-
280
FRN0590E2■-4
250
-
38
325
200×2
-
Note 1) The rated current must be reduced for operation (Rated current x 80%). Recommended wire sizes
assume these conditions.
The recommended wire sizes for the main circuit terminals assume using 75°C 600 V HIV wire.
*1 For compatible crimped terminals, please use model 8-L6 by JST Mfg. Co., Ltd. or equivalent.
*3 For compatible crimped terminals, please use model CB150-10 by JST Mfg. Co., Ltd. or equivalent.
*7 For compatible crimped terminals, please use model 38-6 by JST Mfg. Co., Ltd. or equivalent.
*8 For compatible crimped terminals, please use model 60-6 by JST Mfg. Co., Ltd. or equivalent.
*10 ND-spec.

Table of Contents

Related product manuals