Functional description
Analog output/pulse output
[FM] Analog
monitor
FMV function
FMI function
This terminal outputs analog direct current voltage DC0 to 10 V or analog direct current DC4 to
20 mA / DC0 to 20mA monitor signal. The output form (FMV/FMI) can be switched using SW5
on the printed circuit board and function code F29. Refer to “Table 2.2-31 Functional
Description of Slide switches”.
The signal content can be chosen in the function code F31 data setting among the following
items.
• Output frequency 1 (before slip compensation)
• Output frequency 2 (after slip compensation)
• Output current
• Output voltage
• Output torque
• Load factor
• Input power
• PID feedback value
• Actual speed/estimated speed
• DC link bus voltage
• Universal AO
• Motor output
• Calibration (+)
• PID command (SV)
• PID output (MV)
• Position error in master-follower operation
• Inverter heat sink temperature
• PG feedback value
• Customizable logic ouput signal 1 to 10
* Allowable impedance for connection: Min 5 kΩ (at DC to 10 V output) (up to 2 analog volt
meters (DC0 to 10 V, input impedance 10 kΩ) can be connected.)
* Allowable impedance for connection: Max 500 Ω (at DC4 to 20 mA/DC0 to 20 mA)
* Gain adjustable range: 0 to 300%
Pulse monitor
FMP function
The terminal outputs pulse signal. Signal content can be chosen same as for the FMV function
by function code F31 setting. The output form (FMP) can be switched using SW5 on the printed
circuit board and function code F29. Refer to “Table 2.2-31 Functional Description of Slide
switches”.
* Allowable impedance for connection: Min. 5 kΩ (at DC to 10 V output) (up to 2 analog volt
meters (DC0 to 10 V, input impedance 10 kΩ) can be connected.)
* Pulse duty: Approximately 50%, pulse rate: 25 to 32000 p/s (at full scale)
• Pulse output waveform • FMP output circuit
[FM2] Analog
monitor
FMV2
function
FMI2 function
This terminal outputs analog direct current voltage DC0 to 10 V or analog direct current DC4 to
20 mA (DC0 to 20mA) monitor signal. The output form (FMV2/FMI2) can be switched using
SW7 on the printed circuit board and function code F32. Refer to “Table 2.2-13 Functional
Description of Slide switches”.
The signal content can be chosen in the function code F35 data setting among the same items
with [FM] (F31).
* This terminal is used on the models with the destination codes -GB/-C.
* Allowable impedance for connection: Min 5 kΩ (at DC to 10 V output) (up to 2 analog volt
meters (DC0 to 10 V, input impedance 10 kΩ) can be connected.)
* Allowable impedance for connection: Max 500 Ω (at DC4 to 20 mA/DC0 to 20 mA)
* Gain adjustable range: 0 to 300%
[11] Analog output
common
terminal
This terminal is the common terminal for analog input and analog/pulse output signals. The
terminal is insulated from terminals [CM] and [CMY]. Do not use [CM] and [CMY] as common
terminals for [FM], [FM2].