Pump Control Quick Guide
41
Overpressure alarm (related function codes -> J11, J12 y J13)
Target: make the inverter enter a STOP state and display an error code, when the process value
(Feedback – pressure transducer) rises above a certain level.
Digital Input to use: X4 (with “Enable External alarm Trip” command assigned to it)
Digital Output to use: Y2 (with “PID Alarm” signal assigned to it)
Wiring:
- Connect X4 to Y2
- Connect CMY to PLC (*)
Set-up:
E04 (X4) =
1009: Enable External Alarm Trip (THR)
E21 (Y2) =
42: PID Alarm (PID-ALM)
J12 =
PID Control. Upper Limit Alarm (AH) (%)
J13 =
PID Control. Lower Limit Alarm (AL) (%)
Error Message: when the process value (Feedback Pressure transducer) goes outside of the margin
within J12 (upper limit) or J13 (lower limit), the inverter’s output is switched off and the inverter will
display
OH2
error code. This error can be reset by means of the keypad or by means of a digital input (
8:
“Reset Alarm” (RST))
.
(*) Supposing that the logic of the digital inputs is Active-High Logic (the common of the inputs is PLC
(+24VDC) and inputs’ logic switch is in SOURCE).
If the common of the inputs is terminal CM (0 VDC) (Active-Low Logic in the inputs), please connect the
terminals CMY and CM and set the switch to the SINK position.
Note: Please see function code J11 (PID Control. Select Alarm Output), in order to select other alarm
modes, see the User Manual of the
inverter
.