5.2 Function Code Tables
5-37
FUNCTION CODES
Chap 5
Function
code
Name
Control method and Data setting range
Change when running
Data copying
Factory
default
Related page
d41
Application specific function
selection
0: Disable (Normal control)
1: Enable (Constant surface speed control)
2: Master-follower operation (Immediate synchronization mode at the start,
without Z phase)
3: Master-follower operation (Master-follower operation)
4: Master-follower operation (Immediate synchronization mode at the start,
with Z phase)
N
Y
0
5-305
d51
For adjustment by
manufacturer *9
-500 to 500
N
Y
*14
5-308
d52
For adjustment by
manufacturer *9
-500 to 500
N
Y
*14
d53
For adjustment by
manufacturer *9
-500 to 500
N
Y
*14
d54
For adjustment by
manufacturer *9
-500 to 500
N
Y
*14
d55
For adjustment by
manufacturer *9
0000 to 00FF (Display in hexadecimal)
N
Y
0000
d59
PG option Ch1 /
Terminal [X]
(Pulse train input)
(Pulse input format)
0: Pulse train sign / Pulse train input
1: Forward rotation pulse / Reverse rotation pulse
2: A, B phase 90° phase difference (B phase lead)
3: A, B phase 90° phase difference (A phase lead)
N
Y
0
5-314
d60
(Encoder pulse resolution)
0014 to EA60(Hexadecimal format), 20 to 60000(Decimal format)
N
Y
0400
(1024)
d61
(Filter time constant)
0.000 to 5.000 s
Y
Y
0.005
5-308
d62
(Pulse scaling factor 1)
1 to 32767
Y
Y
1
d63
(Pulse scaling factor 2)
1 to 32767
Y
Y
1
d67
Starting characteristic
(Auto search mode: speed
sensorless vector control)
0: Disable (Do not set to 0 if performing restart after momentary power
failure. Failure to observe this could result in motor damage.)
1: Enable (Only at restart after momentary power failure)
2: Enable (At restart after momentary power failure and at normal start)
If F42 = 15, 2 is automatically set.
N
Y
1
5-308
d68
For adjustment by
manufacturer *9
0.0 to 10.0
N
4.0
5-308
d69
For adjustment by
manufacturer *9
30.0 to 100.0
Y
Y
30.0
d70
Speed control limiter
0.00 to 100.00 %
Y
Y
100.00
5-308
*9: This is a function code for adjustment by the manufacturer. Do not change.
*14: The factory default is set based on capacity. 5 for FRN0018G2S-2G/FRN0009G2-4G or lower inverters, 10 for FRN0032G2S-2G/FRN0018G2
-4G to FRN0115G2S-2G/FRN0060G2-4G inverters, 20 for FRN0146G2S-2G/FRN0075G2-4G or higher inverters