operation when an inverter alarm occurs.
• The sequence functions normally without using “SW52-1”, even if the inverter main power is supplied
constantly.
• If using “SW52-1”, connect control power auxiliary input terminal [R0] and [T0]. If “SW52-1” turns OFF
without using [R0] and [T0], the control power supply will be lost. Furthermore, enable the instant restart
function by setting a value of 2 to 5 for function code F14 to prevent an LV alarm occurring when the
primary power supply is cut off.
• The sequence functions even when an alarm occurs, and may not function normally if the inverter is
damaged. Prepare an external emergency switching circuit for important equipment.
• By turning ON the commercial power supply side contactor (88) and inverter output side (secondary
side) contactor (52-2) simultaneously, the main power supply is input from the inverter output side
(secondary side), and depending on the situation, the inverter may be damaged. Use an interlock for
external circuits.