5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions)
5-182
E50
A60, b60, r60
Speed display coefficient
Speed display coefficient 2, 3, 4
E50 specifies the coefficient that is used when the load shaft speed or line speed is displayed on the LED monitor.
(Refer to the description of E43.)
By selecting a motor, the applied speed display coefficient changes.
If motor 1 is selected:
Load shaft speed [min-1] = (E50: Display coefficient for speed monitor) x (Output frequency Hz)
Line speed [m/min] = (E50: Display coefficient for speed monitor) x (Output frequency Hz)
Data setting range: 0.01 to 200.00
Selected motor
Applied speed display coefficient
Factory default
Motor 1
E50
30.00
Motor 2
A60
0.00 (same value as E52 applied)
Motor 3
b60
0.00 (same value as E52 applied)
Motor 4
r60
0.00 (same value as E52 applied)
E51
Display coefficient for “Input watt-hour data”
E51 specifies a display coefficient (multiplication factor) for displaying the input watt-hour data (5_10) in a part of
maintenance information on the keypad.
Integral power data = Display coefficient (E51 data) x Integral power consumption (100 kWh)
Data setting range: 0.000 (cancel/reset) 0.001 to 9999
By setting E51 = 0.000, integral power consumption and integral power data can be cleared to zero.
Setting E51 data to 0.000 clears the input watt-hour and its data to “0.” After clearing, be sure to restore
E51 data to the previous value; otherwise, input watt-hour data will not be accumulated.