5.3 Description of Function Codes 5.3.5 H codes (High performance functions)
5-214
Motor parameters to be initialized are for motors listed below under V/f control. When the base frequency, rated
voltage, and the number of poles are different from those of the listed motors, or when non-Fuji motors or non-
standard motors are used, change the rated current data to that printed on the motor nameplate.
Motor selection P99/A39/b39/r39
V/f setting
Data = 0, 3, or 4
Fuji standard motor 8-series, other
4 poles, 200 V/50 Hz, 400 V/50 Hz
Data = 1
HP rating motors
4 poles, 230 V/60 Hz, 460 V/60 Hz
Data = 2
Fuji dedicated motors for vector control
4 poles, individual
Data = 5
Fuji premium efficiency motors
4 poles, 200 V/50 Hz, 400 V/50 Hz
Data = 20
Other, synchronous motors
6 poles, individual
Data: 21 to 23
Fuji synchronous motors
6 poles, individual
Data can only be set to 20 to 23 with P99.
By changing P02 with the keypad, take into account that the P02 data automatically updates data of P03,
P05 to P23, P30, P40 to P90, and H46. Similarly, when accessing function code A16/b16/r16 for motor 2
to 4, data of related function codes for each are automatically updated.
The function codes initialized by performing motor constant initialization are as follows.
Motor
selection
Motor 1
Motor 2
Motor 3
Motor 4
Data: 0, 1, 3
to 5
20 to 23
F09, F11, P01, P03,
P05 to P23, P30, P40
to P90, H46, d90
A05, A07, A15, A17,
A19 to A37, A53 to
A56
b05, b07, b15, b17,
b19 to b37, b53 to
b56
r05, r07, r15, r17,
r19 to r37, r53 to r56
Data: 2
The above function
codes + F04, F05
The above function
codes + A02, A03
The above function
codes + b02, b03
The above function
codes + r02, r03