5.3 Description of Function Codes 5.3.5 H codes (High performance functions)
5-228
H30
H31
Link function (Operation selection)
Link function (Actual terminal operation selection)
Related function codes: y94 bus function (Operation command source selection)
y98 bus function (Operation selection)
Using the RS-485 communications link, built-in CAN communications link or fieldbus (option) allows you to issue
frequency settings and run operation commands (run stop/general-purpose digital input) from a computer or PLC
at a remote location, as well as monitor the inverter running information and the function code data. It is possible to
sets the source that specifies the frequency settings and run operation commands with H30, y94, and y98. H30
selects RS-485 communication, and y94 and y98 select the fieldbus setting procedure.
Table 5.3-11 Command sources selectable
Command source
Content
Inverter itself
Sources except RS-485 communications link and fieldbus
Frequency setting: Specified by F01/C30, or multistep frequency command
Run operation command: Keypad, terminal block, etc. set at F02
Via RS-485 communications link
(port 1)
Via RJ-45 connector for keypad connection
Via RS-485 communications link
(port 2)
Via terminal block ([DX+], [DX-], [SD])
Via various types of field Bus
cards (Option)
Via fieldbus (DeviceNet, PROFIBUS DP, etc.)
Table 5.3-12 Command sources specified by H30 (Communications link function, Mode selection)
H30 data
Frequency setting
Run operation command:
0
Inverter itself (F01/C30)
Inverter itself (F02)
1
RS-485 communications link (port 1)
Inverter itself (F02)
2
Inverter itself (F01/C30)
RS-485 communications link (port 1)
3
RS-485 communications link (port 1)
RS-485 communications link (port 1)
4
RS-485 communications link (port 2)
Inverter itself (F02)
5
RS-485 communications link (port 2)
RS-485 communications link (port 1)
6
Inverter itself (F01/C30)
RS-485 communications link (port 2)
7
RS-485 communications link (port 1)
RS-485 communications link (port 2)
8
RS-485 communications link (port 2)
RS-485 communications link (port 2)
Fieldbus (Option)
Setting specified by H30 or
y98 applies when “LE” is
not assigned.
Selected setting
(frequency command
/run command)
“LE”
Inverter
RS-485 communications link
(port 1: RJ-45)
RS-485 communications link
(port 2: Terminal)