5.3 Description of Function Codes 5.3.8 J codes (Applied functions)
5-289
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
Fig. 5.3-36 Operation time chart under v/f control
Fig. 5.3-37 Operation time chart under vector control with speed sensor
J71 can be used even under vector control with speed sensor.
If using with zero speed control under vector control with speed sensor, set the J95 brake-release
torque to 0%.
If the brake is released at zero speed, use torque bias.
If the brake is applied (brake signal OFF) to stop the motor after releasing the brake (brake signal ON)
and performing operation, turn the inverter run command OFF and then back ON again in order to
release the brake (brake signal ON) to resume operation.
The brake release signal is not output during auto tuning (stop mode).
F23: Starting frequency 1
Output frequency
J68: Brake-release current
Output current
Run command
Brake control signal BRKS
Brake-apply frequency/speed
Stop frequency
Stop frequency (holding time)
Brake-release
frequency/speed
Starting frequency 1
(holding time)
Brake-release timer
Brake-apply timer