5.3 Description of Function Codes 5.3.10 U codes (Customizable logic operation)
5-393
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
FUNCTION CODES
Chap 5
Inputs 1 and 2 (U02, U03, etc.)
The following signals are available as analog input signals.
LED
Selectable signals
8000
General-purpose analog output signal (same as signals selected in F31: output
frequency 1, output current, output torque, power consumption, DC intermediate
circuit voltage, etc.)
Example: For output frequency 1, maximum frequency (100 %) is input as 100.00.
Example: For output current, 200 % of the inverter rated current is input 100.00.
Note: 10 (Universal AO) is not available.
to
8026
2001 to 2260
Step 1 to 260 output “SO01” to “SO260”
9001
Analog [12] terminal input signal “12”
9002
Analog [C1] terminal input signal (C1 function) “C1”
9003
Analog [V2] terminal input signal “V2”
9004
Analog [32] terminal input signal “32” (option card, OPC-AIO)
9005
Analog [C2] terminal input signal “C2” (option card, OPC-AIO)
9006,9007
Reserved
9008
Analog [C1] terminal input signal (V3 function) “V3”
9010
UP/DOWN value (when UP/DOWN command valid)UP/DOWN
Function 1, Function 2 (U04, U05, etc.)
Sets the upper limit and lower limit of operation circuit.
LED
Function
Description
-9990.00 to 0.00 to
+9990.00
Reference value
Hysteresis width
Upper limit
Lower limit
Upper threshold
Lower threshold
Setting value
Maximum scale
Minimum scale
Setting values for the operation circuit (selected with the
corresponding function code such as U01).
Conversion factor setting (U92 to U97)
Sets the factor of conversions function (3001, 3002) of operation circuit.
Function
code
Name
Data setting range
Factory
default
U92
Mantissa of K
A
Mantissa: -9.999 to 9.999
0.000
U93
Exponent part of K
A
Exponent part: -5 to 5
0
U94
Mantissa of K
B
0.000
U95
Exponent part of K
B
0
U96
Mantissa of K
c
0.000
U97
Exponent part of K
c
0
U92 to U97 can automatically be calculated based on measured data. For details, refer to the descriptions of U101
to U107 (page 5-408).

Table of Contents