5.3 Description of Function Codes 5.3.10 U codes (Customizable logic operation)
Output signal
Each customizable logic step is output to SO01 to SO260.
SO01 to SO260 differ in configuration depending upon the connection destination, as listed below. To relay those
outputs to any function other than the customizable logic, route them via customizable logic outputs CL01 to CLO14.
Connection destination of each
step output
Internal step output signals “SO01” to “SO260” are
selected by setting the customizable logic input.
Inverter sequence processing
input (digital ON/OFF)
(Multi-step speed “SS1” and
run command “FWD” etc.)
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
Select an inverter’s sequence processor input function to
which one of the customizable logic output signals 1 to 14
(“CL01” to “CLO14”) is to be connected. (Same as in E01)
Analog input
(such as auxiliary frequency
commands or PID process
commands)
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
Select an analog input function to which one of the
customizable logic output signals 1 to 14 (“CL01” to
“CLO14”) is to be connected. (Same as in E61)
General-purpose digital output
(terminal [Y1] to [Y4], [Y5AC],
[30ABC])
Option digital output (terminal
[01] to [08])
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
To specify a general-purpose digital output function (on [Y]
terminals) to which one of the customizable logic output
signals 1 to 14 (“CL01” to “CLO14”) is to be connected,
select one of “CLO1” to “CLO14” by specifying the general-
purpose digital output function on any Y terminal.
General-purpose analog output
(terminal [FM1], [FM2])
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
General-purpose output
(terminal [FMP])
To set general-purpose analog output (terminal [FM1],
[FM2]) or general-purpose pulse output (terminal [FMP]) to
be connected to customizable logic output signal 1 “CLO1”
to 14 “CLO14”, select “CLO1” to “CLO14” at the general-
purpose analog output (terminal [FM1], [FM2]) or general-
purpose pulse output (terminal [FMP]) function selection
side.
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
Select user-defined alarms to be connected to
customizable logic output signals 1 “CLO1” to 14 “CLO14”.
General-purpose digital outputs (on [Y] terminals) are updated every 5 ms. To securely output a
customizable logic signal via [Y] terminals, include on- or off-delay timers in the customizable logic.
Otherwise, short ON or OFF signals may not be reflected on those terminals.