5.3 Description of Function Codes 5.3.10 U codes (Customizable logic operation)
5-398
Output signal
Each customizable logic step is output to SO01 to SO260.
SO01 to SO260 differ in configuration depending upon the connection destination, as listed below. To relay those
outputs to any function other than the customizable logic, route them via customizable logic outputs CL01 to CLO14.
Connection destination of each
step output
Setting method
Function code
Customizable logic input
Internal step output signals “SO01” to “SO260” are
selected by setting the customizable logic input.
U02U03,
etc.
Inverter sequence processing
input (digital ON/OFF)
(Multi-step speed “SS1” and
run command “FWD” etc.)
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
U71 to U80
U181 to
U184
Select an inverter’s sequence processor input function to
which one of the customizable logic output signals 1 to 14
(“CL01” to “CLO14”) is to be connected. (Same as in E01)
U81 to U90
U185 to
U188
Analog input
(such as auxiliary frequency
commands or PID process
commands)
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
U71 to U80
U181 to
U184
Select an analog input function to which one of the
customizable logic output signals 1 to 14 (“CL01” to
“CLO14”) is to be connected. (Same as in E61)
U81 to U90
U185 to
U188
General-purpose digital output
(terminal [Y1] to [Y4], [Y5AC],
[30ABC])
Option digital output (terminal
[01] to [08])
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
U71 to U80
U181 to
U184
To specify a general-purpose digital output function (on [Y]
terminals) to which one of the customizable logic output
signals 1 to 14 (“CL01” to “CLO14”) is to be connected,
select one of “CLO1” to “CLO14” by specifying the general-
purpose digital output function on any Y terminal.
E20 to E24
E27
General-purpose analog output
(terminal [FM1], [FM2])
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
U71 to U80
U181 to
U184
General-purpose output
(terminal [FMP])
To set general-purpose analog output (terminal [FM1],
[FM2]) or general-purpose pulse output (terminal [FMP]) to
be connected to customizable logic output signal 1 “CLO1”
to 14 “CLO14”, select “CLO1” to “CLO14” at the general-
purpose analog output (terminal [FM1], [FM2]) or general-
purpose pulse output (terminal [FMP]) function selection
side.
F31, F61
F35
User-defined alarm
Select one of the internal step output signals “SO01” to
“SO260” to be connected to customizable logic output
signals 1 to 14 (“CL01” to “CLO14”).
U71 to U80
U181 to
U184
Select user-defined alarms to be connected to
customizable logic output signals 1 “CLO1” to 14 “CLO14”.
U81 to U90
U185 to
U188
General-purpose digital outputs (on [Y] terminals) are updated every 5 ms. To securely output a
customizable logic signal via [Y] terminals, include on- or off-delay timers in the customizable logic.
Otherwise, short ON or OFF signals may not be reflected on those terminals.