5.2 Function Code Tables
5-9
Function
Code Tables
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Chapter 5 Function Code
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
E30 Frequency Arrival (Detection width) 0.0 to 10.0 Hz Y Y 2.5 Y Y Y Y N 5-152
E31 Frequency Detection (Operation
level)
0.0 to 500.0 Hz Y Y 60.0 Y Y Y Y Y
5-153
E32 (Hysteresis width) 0.0 to 500.0 Hz Y Y 1.0 Y Y Y Y Y
E34 Overload Early Warning/Current
Detection (Operation level)
0.00 (Disable); 1% to 200% of the inverter rated current Y Y1, Y2 *3 Y Y Y Y Y 5-153
E35 (Timer) 0.01 to 600.00 s Y Y 10.00 Y Y Y Y Y
E36 Frequency Detection 2 (Operation
level)
0.0 to 500.0 Hz Y Y 60.0 Y Y Y Y Y
5-154
E37 Current Detection 2/Low Current
Detection (Operation level)
0.00 (Disable); 1% to 200% of the inverter rated current Y Y1, Y2 *3 Y Y Y Y Y
E38 (Timer) 0.01 to 600.00 s Y Y 10.00 Y Y Y Y Y
E40 PID Display Coefficient A -999 to 0.00 to 9990 Y Y 100 Y Y Y Y N 5-155
E41 PID Display Coefficient B -999 to 0.00 to 9990 Y Y 0.00 Y Y Y Y N
E42 LED Display Filter 0.0 to 5.0 s Y Y 0.5 Y Y Y Y Y 5-156
E43 LED Monitor (Item selection) 0: Speed monitor (select by E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Power consumption
10: PID command
12: PID feedback value
14: PID output
15: Load factor
16: Motor output
17: Analog input monitor
23: Torque current (%)
24: Magnetic flux command value (%)
25: Integral power consumption
Y Y 0 Y Y Y Y Y 5-157
E44 (Display when stopped) 0: Specified value 1: Output value Y Y 0 Y Y Y Y Y 5-158
E45 LCD Monitor (Item selection) 0: Running status, rotational direction and operation guide
1: Bar charts for output frequency, current and calculated torque
Y Y 0 Y Y Y Y Y
E46 (Language selection) 0: Japanese
1: English
2: German
3: French
4: Spanish
5: Italian
Y Y 0 Y Y Y Y Y
E47 (Contrast control) 0 (Low) to 10 (High) Y Y 5 Y Y Y Y Y
E48 LED Monitor (Speed monitor
selection)
0: Output frequency 1 (Before slip compensation)
1: Output frequency 2 (After slip compensation)
2: Reference frequency
3: Motor speed
4: Load shaft speed
5: Line speed
7: Display speed (%)
Y Y 0 Y Y Y Y Y 5-157
5-158
E49 Torque Monitor (Polarity selection) 0: Torque polarity
1: + for drive, - for brake
Y Y 1 Y Y Y Y Y 5-159
E50 Coefficient for speed indication 0.01 to 200.00 Y Y 30.00 Y Y Y Y Y 5-160
E51 Display Coefficient for Integral
Power Data
0.000 (Cancel/reset), 0.001 to 9999 Y Y 0.010 Y Y Y Y Y
E52 Keypad Menu Selection 0: Function code data setting mode (Menus #0, #1, and #7)
1: Function code data check mode (Menu #2 and #7) Full-menu mode
2: Full-menu mode
Y Y 0 Y Y Y Y Y 5-161
E54 Frequency Detection 3 (Operation
level)
0.0 to 500.0 Hz Y Y 60.0 Y Y Y Y Y
5-153
E55 Current Detection 3 (Operation
level)
0.00 (Disable); 1% to 200% of the inverter rated current
Y Y1, Y2 *3 Y Y Y Y Y
5-161
E56 (Timer) 0.01 to 600.00 s Y Y 10.00 Y Y Y Y Y
E 61 Terminal [12] Extended Function N Y 0 Y Y Y Y Y 5-162
E 62 Terminal [C1] N Y 0 Y Y Y Y Y
E 63 Terminal [V2]
0: No assignment
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID process command 1
5: PID feedback value
6: Ratio setting
7: Analog torque limit value A
8: Analog torque limit value B
10: Torque command
11: Torque current command
17: Forward (FWD) side speed limit value
18: Reverse (REV) side speed limit value
20: Analog input monitor
N Y 0 Y Y Y Y Y
E64 Saving of Digital Reference
Frequency
0: Automatic saving (when main power is turned OFF)
1: Saving by pressing
key
Y Y 1 Y Y Y Y Y 5-163
E65 Reference Loss Detection
(Continuous running frequency) 0: Decelerate to stop, 20% to 120%, 999: Cancel Y Y 999 Y Y Y Y Y
E76 DC Medium Voltage Detection Level 200 to 400 V: (200 V class series)
400 to 800 V: (400 V class series)
Y Y2 235
470
Y Y Y Y Y
E78 Torque Detection 1 (Operation level) 0 to 300% Y Y 100 Y Y Y Y Y 5-164
E79 (Timer) 0.01 to 600.00 s Y Y 10.00 Y Y Y Y Y
E80 Torque Detection 2/
Low Torque Detection (Operation
level)
0 to 300% Y Y 20 Y Y Y Y Y
E81 (Timer) 0.01 to 600.00 s Y Y 20.00 Y Y Y Y Y
The shaded function codes ( ) are applicable to the quick setup.
*3 The motor rated current is automatically set. See Table 5.2-18.