5.2 Function Code Tables
5-10
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
E98 Terminal [FWD] Function 0 (1000): Select multi-frequency (0 to 1 step) (SS1) N Y 98 Y Y Y Y N 5-122
E99 Terminal [REV] Function
1 (1001): Select multi-frequency (0 to 3 steps) (SS2) N Y 99 Y Y Y Y N
5-165
2 (1002): Select multi-frequency (0 to 7 steps) (SS4) Y Y Y Y N
3 (1003): Select multi-frequency (0 to 15 steps) (SS8) Y Y Y Y N
4 (1004): Select ACC/DEC time (2 steps) (RT1) Y Y Y Y N
5 (1005): Select ACC/DEC time (4 steps) (RT2) Y Y Y Y N
6 (1006): Self-hold (HLD) Y Y Y Y Y
7 (1007): Coast to a stop (BX) Y Y Y Y Y
8 (1008): Reset alarm (RST) Y Y Y Y Y
9 (1009): External alarm (THR)
(9 = Active OFF, 1009 = Active ON)
Y Y Y Y Y
10 (1010): Ready for jogging (JOG) Y Y Y Y N
11 (1011): Select frequency command 2/1 (Hz2/Hz1) Y Y Y Y N
12 (1012): Select motor 2 (M2) Y Y Y Y Y
13: DC braking command (DCBRK) Y Y Y Y N
14 (1014): Torque limit 2/1 (TL2/TL1) Y Y Y Y Y
15: Switch to commercial power (50 Hz) (SW50) Y Y N N N
16: Switch to commercial power (60 Hz) (SW60) Y Y N N N
17 (1017): UP command (UP) Y Y Y Y N
18 (1018): DOWN command (DOWN) Y Y Y Y N
19 (1019): Enable data change with keypad (data can be modified)
(WE-KP)
Y Y Y Y Y
20 (1020): Cancel PID control (Hz/PID) Y Y Y Y N
21 (1021): Switch normal/inverse operation (IVS) Y Y Y Y N
22 (1022): Interlock (IL) Y Y Y Y Y
23 (1023): Cancel torque control (Hz/TRQ) N N N N Y
24 (1024): Enable communications link via RS-485 or fieldbus (optional)
(LE)
Y Y Y Y Y
25 (1025): Universal DI (U-DI) Y Y Y Y Y
26 (1026): Start characteristics selection (STM) Y Y Y N Y
30 (1030): Force to stop (STOP)
(30 = Active OFF, 1030 = Active ON)
Y Y Y Y Y
32 (1032): Pre-excitation (EXITE) N N Y Y N
33 (1033): Reset PID integral and differential components (PID-RST) Y Y Y Y N
34 (1034): Hold PID integral component (PID-HLD) Y Y Y Y N
35 (1035): Select local (keypad) operation (LOC) Y Y Y Y Y
36 (1036): Select motor 3 (M3) Y Y Y Y Y
37 (1037): Select motor 4 (M4) Y Y Y Y Y
39: Protect motor from dew condensation (DWP) Y Y Y Y Y
40: Enable integrated sequence to switch to commercial power
(50 Hz) (ISW50)
Y Y N N N
41: Enable integrated sequence to switch to commercial power
(60 Hz) (ISW60)
Y Y N N N
47 (1047): Servo-lock command (LOCK) N N N Y N
49 (1049): Pulse train sign (SIGN) Y Y Y Y Y
59 (1059): Enable battery-driven operation (BATRY) Y Y Y Y Y
70 (1070): Cancel constant peripheral speed control (Hz/LSC) Y Y Y Y N
71 (1071): Hold the constant peripheral speed control frequency in the
memory (LSC-HLD)
Y Y Y Y N
72 (1072): Count the run time of commercial power-driven motor 1
(CRUN-M1)
Y Y N N Y
73 (1073): Count the run time of commercial power-driven motor 2
(CRUN-M2)
Y Y N N Y
74 (1074): Count the run time of commercial power-driven motor 3
(CRUN-M3)
Y Y N N Y
75 (1075): Count the run time of commercial power-driven motor 4
(CRUN-M4)
Y Y N N Y
76 (1076): Select droop control (DROOP) Y Y Y Y N
77 (1077): Cancel PG alarm (PG-CCL) N Y N Y Y
80 (1080): Cancel customizable logic (CLC) Y Y Y Y Y
81 (1081): Clear all customizable logic timers (CLTC) Y Y Y Y Y
98: Run/stop forward (FWD) Y Y Y Y Y
99: Run/stop reverse (REV) Y Y Y Y Y
100: No function assigned (NONE) Y Y Y Y Y
110 (1110): Select servo-lock gain (SLG2) N N N Y N
111 (1111): Force to stop (terminal block only) (STOP-T)
(111 = Active OFF, 1111 = Active ON)
Y Y Y Y Y
* Setting the value in parentheses ( ) shown above assigns a negative
logic output to a terminal. (True if OFF.)