EasyManua.ls Logo

Fuji Electric Frenic Mega Series - Page 192

Fuji Electric Frenic Mega Series
774 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.2 Function Code Tables
5-11
Function
Code Tables
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Chapter 5 Function Code
Table 5.2-7
C codes: Control Functions of Frequency
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
C01 Jump Frequency 1 0.0 to 500.0 Hz Y Y 0.0 Y Y Y Y N 5-166
C02 2 Y Y 0.0 Y Y Y Y N
C03 3 Y Y 0.0 Y Y Y Y N
C04 (Width) 0.0 to 30.0 Hz Y Y 3.0 Y Y Y Y N
C05 Multi-frequency 1 0.00 to 500.00 Hz Y Y 0.00 Y Y Y Y N
C06 2 Y Y 0.00 Y Y Y Y N
C07 3 Y Y 0.00 Y Y Y Y N
C08 4 Y Y 0.00 Y Y Y Y N
C09 5 Y Y 0.00 Y Y Y Y N
C10 6 Y Y 0.00 Y Y Y Y N
C11 7 Y Y 0.00 Y Y Y Y N
C12 8 Y Y 0.00 Y Y Y Y N
C13 9 Y Y 0.00 Y Y Y Y N
C14 10 Y Y 0.00 Y Y Y Y N
C15 11 Y Y 0.00 Y Y Y Y N
C16 12 Y Y 0.00 Y Y Y Y N
C17 13 Y Y 0.00 Y Y Y Y N
C18 14 Y Y 0.00 Y Y Y Y N
C19 15 Y Y 0.00 Y Y Y Y N
C20 Jogging Frequency 0.00 to 500.00 Hz Y Y 0.00 Y Y Y Y N 5-168
C21 Pattern operation (Mode selection) 0: One-cycle operation
1: Repeated operation
2: Low-speed operation after one-cycle operation
N Y 0 Y Y Y Y N
C22 (Stage 1 run time) Y Y 0.00 Y Y Y Y N
C23 (Stage 2 run time) Y Y 0.00 Y Y Y Y N
C24 (Stage 3 run time) Y Y 0.00 Y Y Y Y N
C25 (Stage 4 run time) Y Y 0.00 Y Y Y Y N
C26 (Stage 5 run time) Y Y 0.00 Y Y Y Y N
C27 (Stage 6 run time) Y Y 0.00 Y Y Y Y N
C28 (Stage 7 run time)
0.00 to 6000 s
Y Y 0.00 Y Y Y Y N
C30 Frequency Command 2 0: Enable / keys on the keypad
1: Voltage input to terminal [12] (0 to ±10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12] and [C1]
5: Voltage input to terminal [V2] (0 to ±10 VDC)
7: UP/DOWN control
8: Enable
/ keys on the keypad
(balanceless-bumpless switching available)
10: Pattern operation
11: Digital input interface card (option)
12: Pulse train input
N Y 2 Y Y Y Y N 5-62
5-173
C31 Analog Input Adjustment for [12]
(Offset)
-5.0 to 5.0% Y* Y 0.0 Y Y Y Y Y 5-173
C32 (Gain) 0.00 to 200.00% (ROM version earlier than 2000)
0.00 to 400.00% (ROM version 2000 or later)
Y* Y 100.00 Y Y Y Y Y
C33 (Filter) 0.00 to 5.00 s Y Y 0.05 Y Y Y Y Y
C34 (Gain base point) 0.00 to 100.00% Y* Y 100.00 Y Y Y Y Y
C35 (Polarity) 0: Bipolar 1: Unipolar N Y 1 Y Y Y Y Y
C36 Analog input adjustment for [C1]
(Offset)
-5.0 to 5.0% Y* Y 0.0 Y Y Y Y Y
C37 (Gain) 0.00 to 200.00% (ROM version earlier than 2000)
0.00 to 400.00% (ROM version 2000 or later)
Y* Y 100.00 Y Y Y Y Y
C38 (Filter) 0.00 to 5.00 s Y Y 0.05 Y Y Y Y Y
C39 (Gain base point) 0.00 to 100.00% Y* Y 100.00 Y Y Y Y Y
C40 Terminal [C1] Range Selection 0: 4 to 20 mA 1: 0 to 20 mA N Y 0 Y Y Y Y Y
C41 Analog input adjustment for [V2]
(Offset)
-5.0 to 5.0% Y* Y 0.0 Y Y Y Y Y
C42 (Gain) 0.00 to 200.00% (ROM version earlier than 2000)
0.00 to 400.00% (ROM version 2000 or later)
Y* Y 100.00 Y Y Y Y Y
C43 (Filter) 0.00 to 5.00 s Y Y 0.05 Y Y Y Y Y
C44 (Gain base point) 0.00 to 100.00% Y* Y 100.00 Y Y Y Y Y
C45 (Polarity)
0: Bipolar 1: Unipolar
N Y 1 Y Y Y Y Y
C50 Bias (Frequency command 1)
(Bias base point)
0.00 to 100.00% Y* Y 0.00 Y Y Y Y Y 5-62
5-174
C51 Bias (PID command 1)
(Bias base point)
-100.00 to 100.00% Y* Y 0.00 Y Y Y Y Y 5-174
C52 (Bias base point) 0.00 to 100.00% Y* Y 0.00 Y Y Y Y Y
C53 Selection of Normal/Inverse
Operation (Frequency command 1)
0: Normal operation 1: Inverse operation
Y Y 0 Y Y Y Y Y
C82 Pattern operation
(Stage 1 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C83
(Stage 2 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C84
(Stage 3 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C85
(Stage 4 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C86
(Stage 5 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C87
(Stage 6 rotation direction, ACC/DEC time)
Y Y 1 Y Y Y Y N
C88
(Stage 7 rotation direction, ACC/DEC time)
1: Forward, ACC time F07, DEC time F08
2: Forward, ACC time E10, DEC time E11
3: Forward, ACC time E12, DEC time E13
4: Forward, ACC time E14, DEC time E15
11: Forward, ACC time F07, DEC time F08
12: Forward, ACC time E10, DEC time E11
13: Forward, ACC time E12, DEC time E13
14: Forward, REV time E14, DEC time E15
Y Y 1 Y Y Y Y N

Table of Contents