5.2 Function Code Tables
5-15
Chapter 5 Function Code
Function
Code Tables
F codes
E codes
C codes
P codes
H codes
A codes
b codes
r codes
J codes
d codes
U codes
y codes
Table 5.2-10
A codes: Motor 2 Parameters
Drive control
Code Name Data setting range
Change
when
running
Data
copying
Default
setting
V/f
PG
V/f
w/o
PG
w/
PG
To rq ue
control
Refer to
page:
A01 Maximum Output Frequency 2 25.0 to 500.0 Hz N Y 60.0 Y Y Y Y Y
A02 Base Frequency 2 25.0 to 500.0 Hz N Y 50.0 Y Y Y Y Y
A03 Rated Voltage at Base Frequency 2 0: AVR disabled (Output a voltage in proportion to input
voltage)
80 to 240 V: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500 V: Output an AVR-controlled voltage
(for 400 V class series)
N Y2 200
400
Y Y Y Y Y
A04 Maximum Output Voltage 2 80 to 240 V: Output an AVR-controlled voltage
(for 200 V class series)
160 to 500 V: Output an AVR-controlled voltage
(for 400 V class series)
N Y2 200
400
Y Y N N Y
A05 Torque Boost 2 0.0% to 20.0% (percentage with respect to Rated Voltage at Base
Frequency 2)
Y Y *2 Y Y N N N
A06 Electronic Thermal Overload
Protection for Motor 2
(Select motor characteristics)
1: Enable (For a general-purpose motor with shaft-driven cooling fan)
2: Enable (For an inverter (FV)-driven motor with separately powered
cooling fan)
Y Y 1 Y Y Y Y Y
A07 (Operation level) 0.00 (Disable), 1% to 135% of the rated current of the inverterr Y Y1, Y2 *3 Y Y Y Y Y
A08 (Thermal time constant) 0.5 to 75.0 min Y Y *4 Y Y Y Y Y
A09 DC Braking 2
(Braking starting frequency)
0.0 to 60.0 Hz Y Y 0.0 Y Y Y Y N
A10 (Operation level) 0% to 100% (HD mode), 0% to 80% (MD/LD mode) Y Y 0 Y Y Y Y N
A11 (Braking time) 0.00 (Disable): 0.01 to 30.00 s Y Y 0.00 Y Y Y Y N
A12 Starting Frequency 2 0.0 to 60.0Hz Y Y 0.5 Y Y Y Y N
A13 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 2
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto-energy saving operation (Variable torque load during ACC/DEC)
4: Auto-energy saving operation (Constant torque load during ACC/DEC)
5: Auto-energy saving operation (Auto-torque boost during ACC/DEC)
N Y 1 Y Y N Y N
A14 Drive Control Selection 2 0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
3: V/f control with speed sensor
4: Dynamic torque vector control with speed sensor
5: Vector control without speed sensor
6: Vector control with speed sensor
N Y 0 Y Y Y Y Y
A15 Motor 2 (No. of poles) 2 to 22 poles N Y1, Y2 4 Y Y Y Y Y
A16 (Rated capacity) 0.01 to 1000 kW (when A39 = 0 or 2 to 4)
0.01 to 1000 HP (when A39 = 1)
N Y1, Y2 *6 Y Y Y Y Y
A17 (Rated current) 0.00 to 2000 A N Y1, Y2 *6 Y Y Y Y Y
A18 (Auto-tuning) 0: Disable
1: Tune while the motor stops. (%R1, %X and rated slip frequency)
2: Tune the motor while it is rotating under V/f control (%R1, %X and
rated slip frequency, no-load current, magnetic saturation factors 1
to 5, magnetic saturation extension factors "a" to "c")
3: Tune the motor while it is rotating under vector control (%R1, %X
and rated slip frequency, no-load current, magnetic saturation
factors 1 to 5, magnetic saturation extension factors "a" to "c";
enabled under vector control only)
N N 0 Y Y Y Y Y
A19 (Online tuning) 0: Disable 1: Enable Y Y 0 Y N N N N
A20 (No-load current) 0.00 to 2000 A N Y1, Y2 *6 Y Y Y Y Y
A21 (%R1) 0.00 to 50.00% Y Y1, Y2 *6 Y Y Y Y Y
A22 (%X) 0.00 to 50.00% Y Y1, Y2 *6 Y Y Y Y Y
A23 (Slip compensation gain for driving) 0.0 to 200.0% Y* Y 100.0 Y Y Y Y N
A24 (Slip compensation response time) 0.01 to 10.00 s Y Y1, Y2 0.12 Y Y N N N
A25 (Slip compensation gain for braking) 0.0 to 200.0% Y* Y 100.0 Y Y Y Y N
A26 (Rated slip frequency) 0.00 to 15.00 Hz N Y1, Y2 *6 Y Y Y Y N
A27 (Iron loss factor 1) 0.00 to 20.00% Y Y1, Y2 *6 Y Y Y Y Y
A28 (Iron loss factor 2) 0.00 to 20.00% Y Y1, Y2 0.00 Y Y Y Y Y
A29 (Iron loss factor 3) 0.00 to 20.00% Y Y1, Y2 0.00 Y Y Y Y Y
A30 (Magnetic saturation factor 1) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
A31 (Magnetic saturation factor 2) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
A32 (Magnetic saturation factor 3) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
A33 (Magnetic saturation factor 4) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
A34 (Magnetic saturation factor 5) 0.0 to 300.0% Y Y1, Y2 *6 Y Y Y Y Y
A35 (Magnetic saturation extension factor
"a")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
A36 (Magnetic saturation extension factor
"b")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
A37 (Magnetic saturation extension factor
"c")
0.0 to 300.0%
Y Y1, Y2 *6 Y Y Y Y Y
A39 Motor 2 Selection 0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
2: Motor characteristics 2 (Fuji motors exclusively designed for vector
control)
3: Motor characteristics 3 (Fuji standard motors, 6-series)
4: Other motors
N Y1, Y2 0 Y Y Y Y Y
*2 The factory default differs depending upon the inverter's capacity. See Table 5.2-17.
*3 The motor rated current is automatically set. See Table 5.2-18 (function code P03).
*4 5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
*6 The motor parameters are automatically set, depending upon the inverter's capacity. See Table 5.2-18.