Function Settings
Func.
code
Name Data setting range Factory settingMin. Unit
Extension Terminal Functions: E codes
Selects from the following items by code.
0 : (1000) Multistep freq. selection (0 to 1 step)
1 : (1001) Multistep freq. selection (0 to 3 step)
2 : (1002) Multistep freq. selection (0 to 7 step)
4 : (1004) ACC/DEC time selection (2 steps)
6 : (1006) 3-wire operation stop command
7 : (1007) Coast-to-stop command
8 : (1008) Alarm reset
9 : (1009) Trip command (External fault)
10 : (1010) Jogging operation
11 : (1011) Freq. set 2 / Freq. set 1
19 : (1019) Write enable for keypad (Data changeable)
20 : (1020) PID control cancel
21 : (1021) Normal/Inverse mode changeover
24 : (1024) Link enable (RS-485 (standard), BUS (option))
33 : (1033) PID integration/differentiation reset
34 : (1034) PID integration hold
*The number in ( ) indicates logical inverse. (OFF when short-circuited)
[SS1]
[SS2]
[SS4]
[RT1]
[HLD]
[BX]
[RST]
[THR]
[JOG]
[Hz2/Hz1]
[WE-KP]
[Hz/PID]
[IVS]
[LE]
[PID-RST]
[PID-HLD]
--
0
--
7
--
8
Terminal Command Assignment to: [X1]
[X2]
[X3]
(Mechanical relay contacts)
Selects from the following items by code.
0 : (1000) Inverter running
1 : (1001) Frequency equivalence signal
2 : (1002) Frequency level detection
3 : (1003) Undervoltage detection signal
5 : (1005) Torque limiting (Current limiting)
6 : (1006) Auto-restarting
7 : (1007) Motor overload early warning
26 : (1026) Retry in operation
30 : (1030) Lifetime alarm
35 : (1035) Inverter running
36 : (1036) Overload preventive control
37 : (1037) Current detection
41 : (1041) Low level current detection
99 : (1099) Alarm relay output (for any fault)
*The number in ( ) indicates logical inverse. (OFF when short-circuited)
[RUN]
[FAR]
[FDT]
[LV]
[IOL]
[IPF]
[OL]
[TRY]
[LIFE]
[RUN2]
[OLP]
[ID]
[IDL]
[ALM]
--
0
--
99
Status Signal Assignment to: [Y1]
[30A, B, C]
0 : Speed monitor (select by E48)
3 : Output current
4 : Output voltage
9 : Input power
10 : PID final command value
12 : PID feedback value
13 : Timer value (timer operation)
--
0
Monitor Item Selection
0 : Output frequency (before slip compensation)
1 : Output frequency (after slip compensation)
2 : Setting frequency
4 : Load shaft speed
5 : Line speed
6 : Constant rate of feeding time
--
0
LED Monitor
(Speed monitor item)
(Menu display mode)
0.01 to 200.00
0.01
-
30.00
Coefficient for Speed Indication
0 : Function code data setting menu only
1 : Data verification menu only
2 : All menu
--
0
Keypad
See Note 2.
(Detection level)
0.00 to 3600s
0.01 s 6.00
Acceleration Time 2
0.00 to 3600s
0.01 s 6.00
Deceleration Time 2
0.0 to 400.0Hz
0.1 Hz 60.0
Frequency Detection (FDT)
0.000 to 9.999 0.001
-
0.000
Coefficient for Constant Feeding Rate Time
10.00
(Level)
(Timer)
Overload Early Warning/Current Detection/
Low Current Detection
Current Detection/Low Current
Detection
0.00(Inactive), 1 to 200% of inverter rated current 0.01 A Rated current of
Fuji's standard motor
0.01 to 600.00s 0.01 s
100
0.00
PID Display Coefficient A
PID Display Coefficient B
-999 to 0.00 to 999 0.01
-
-999 to 0.00 to 999 0.01
-
Note 1: The above setting ranges may be limited by the signs or the number of digits.
Note 2: The inverter does not use the codes to though they are displayed.
<Changing, reflecting or storing data during operation>
: Disable : Change with keys and then save or reflect with key. : Change or reflect with keys and then save with key.
21