5-46
If P99 (Motor selection) is set to 1 (HP motors):
Rated current (A)
If P99 (Motor selection) is set to:
Setting
range
(HP)
1
Shipping destination (Version)
Power
supply
voltage
Function
code
P02
Nomi-
nal
applied
motor
(HP)
Asia EU Japan
0.01 to 0.10 0.1 0.44 0.44 0.44
0.11 to 0.12
0.12 0.68 0.68 0.68
0.13 to 0.25
0.25 1.40 1.40 1.40
0.26 to 0.50
0.5 2.00 2.00 2.00
0.51 to 1.00
1 3.00 3.00 3.00
1.01 to 2.00
2 5.80 5.80 5.80
2.01 to 3.00
3 7.90 7.90 7.90
3.01 to 5.00
5 12.60 12.60 12.60
5.01 to 7.50
7.5 18.60 18.60 18.60
Three-phase 200 V
Single-phase 200 V
Single-phase 100 V
7.51 to 10.00
10 25.30 25.30 25.30
0.01 to 0.10 0.1 0.22 0.22 0.22
0.11 to 0.12
0.12 0.34 0.34 0.34
0.13 to 0.25
0.25 0.70 0.70 0.70
0.26 to 0.50
0.5 1.00 1.00 1.00
0.51 to 1.00
1 1.50 1.50 1.50
1.01 to 2.00
2 2.90 2.90 2.90
2.01 to 3.00
3 4.00 4.00 4.00
3.01 to 5.00
5 6.30 6.30 6.30
5.01 to 7.50
7.5 9.30 9.30 9.30
Three-phase 400 V
7.51 to 10.00
10 12.70 12.70 12.70
NOTE: The rated current will be initialized to the value for motors rated for 230 V
or 460 V at 60 Hz. If the base frequency or rated voltage is different, change the
P03 data to the rated current printed on the nameplate.