9-102
< Biannual maintenance >
After the current setting has expired, set a value for the next maintenance in H78
and press the
key so that the output signal is reset and counting restarts.
This function is exclusively applies to the 1st motor.
Check the cumulative motor run time with
5_23
on Menu #5 "Maintenance
Information" of the keypad. Similarly, check the time remaining before the next
maintenance with
5_31
.
H79 Preset Startup Count for Maintenance (M1) H44 (Startup Counter for Motor 1)
H79 specifies the number of inverter startup times to determine the next maintenance timing,
e.g., for replacement of a belt.
Set the H79 and H44 data in hexadecimal. The maximum setting count is 65,535 (FFFF in
hexadecimal.)
- Data setting range: 0000 (Disable); 0001 to FFFF (Hexadecimal)
Maintenance timer -- MNT (E20 and E27, data = 84)
When the count of the startup counter for motor 1 (H44) reaches the number specified by H79
(Preset startup count for maintenance (M1)), the inverter outputs the maintenance timer
signal MNT (if assigned to any digital terminal with any to E20 and E27) to remind the user
of the need of the maintenance of the mechanical system.
< Maintenance every 1,000 times of startups >