6-1
6 Specifications
6-1 Standard specifications
6-1-1 DB unit
Series 200V 400V
Type BU37-2C
BU55-2C
BU90-2C
BU37-4C
BU55-4C
BU90-4C
BU132-4C
BU220-4C
Min. connectable
resistance (Ω)
3.0 2.0 1.2 12 7.5 4.7 3.0 1.9
Max. braking power
(kW)
37 56 90 37 56 90 135 240
Generated loss
(10%ED) (W)
40 50 60 35 40 50 60 80
Rated current
(A r.m.s)
25 37 61 12 19 31 47 79
Mass (kg) 4 6 9 4 5.5 5.5 9 13
Braking torque 100% (at standard applying to G11S)
Duty factor 10%ED (30%ED when using option fans)
∗1, ∗2
Braking time 10s: Period of 100s (30s when using option fans)
∗1, ∗2
Operating voltage (V)
365 758
Protection function
• Blown fuse
• Cooling fin overheat
• Abnormal operation of IGBT
(Switching element)
• Braking resistor overheat
When detecting abnormalities described left,
the operation of the IGBT in the DB unit is
stopped, and an alarm is output to the inverter
unit
Cooling system Self-ventilation (forced ventilation when using option fans)
Installation location
Indoor
Altitude of 1000m or less
Free from corrosive gas. dust and direct sunlight
Ambient temperature
−10℃ to +50℃
∗
1) Duty factor (%ED) and braking time are converted into the condition of deceleration braking as shown
below.
Duty factor
%ED=( T1/T0 ) X 1 00%
T1 : Braking time (10s)
T0 : Repetitive period (100s)
T1 T1
T0
Braking power
power
The rated current value is an r.m.s value of the current in TD section.
∗
2) When using the option fans, the duty factor (%ED) is calculated making the braking time (T1) 30s.
※ This DB unit are applicable to the following inverter units.
・200V series: FRENIC5000 G5/P5,G7/P7,G9S/P9S,G11S/P11S series
FRENIC-Eco series, FRENIC5000 VG3,VG 5, VG7S series
・400V series: RENIC5000 G9S/P9S,G11S/P11S series, FRENIC-Eco series
FRENIC5000 VG5 series