Conformity to the Low Voltage Directive in the EU
If installed according to the guidelines given below, inverters marked with CE are considered as
compliant with the Low Voltage Directive 2006/95/EC.
12. Use wires listed in IEC60364-5-52.
Recommended wire size (mm
2
)
*1
Rated current (A)
of
MCCB or RCD/ELCB
*2
Main circuit
power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Grounding [
G]
Power supply voltage
Appli-
cable
motor
rating
(HP)
Inverter type
w/ DCR
*3
w/o DCR
w/ DCR
*3
w/o DCR
*2
Inverter
output
[U, V,
W]
*2
DCR
[P1,
P (+)]
Braking
resistor
[P (+),
DB]
Control
circuit
(30A,
30B,
30C)
7.5
FRN0025C2S-2U 30 50 4.0 6.0 4.0 4.0
10
FRN0033C2S-2U 40 75 6.0 10 6.0 6.0
15
FRN0047C2S-2U 50 100 10 16 10 16
3-phase 200 V
20
FRN0060C2S-2U 75 125 16 25 16 25
0.5
7.5
FRN0013C2S-4U 15 30 2.5
10
FRN0018C2S-4U 20 40
2.5
4.0
2.5 2.5
15
FRN0024C2S-4U 30 50 4.0 6.0 4.0 4.0
3-phase 400 V
20
FRN0030C2S-4U 40 60 6.0 10 6.0 6.0
0.5
MCCB: Molded case circuit breaker
RCD: Residual-current-operated protective device
ELCB: Earth leakage circuit breaker
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, de-
pending on the power transformer capacity. Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70
C 600V PVC wires used at an ambient
temperature of 40
C.
*3 In the case of no DC reactor, the wire sizes are determined on the basis of the effective input current
calculated under the condition that the power supply capacity and impedance are 500 kVA and
5%, respectively.