2 Installation and Connection 2-5
FVR-C11S-EN
2
3) DC reactor connectin
terminal [P1, P(+)]
1. Use this terminal to connect a input power-
factor correctin
DC reactor (optional).
Remove the jumper connected in the fac-
tor
before connectin
the DC reactor (see
Fi
ure 2-3-2).
a) Connection dia
ram
b) Cuttin
of barrier
Fi
ure 2-3-2 Connection of DC reactor
2. Use dia
onal cuttin
pliers to cut the sur-
face cover barriers from P1, P(+) terminals
before connection.
3. If no DC reactor is used, do not remove the
jumper.
4) Inverter
roundin
terminal [ G]
Alwa
s
round the inverter
roundin
termi-
nal [ G] for safet
and noise reduction.
Groundin
of the metal frames of electric
equipment has to be done in accordance with
the national and local safet
specifications in
force.
1. In Japan, the 200V s
stem must be con-
nected to a
round electrode provided with
class D
roundin
, accordin
to the electri-
cal equipment technical standard.
Table 2-3-2 Groundin
of device accordin
to
electrical equipment technical standard
2. Connect a thick and short wire to the
roundin
terminal of the inverter for con-
nection with a
round electrode prepared
exclusivel
for the inverter s
stem.
P(+)
P1
FVR-C11S-7EN
Top of inverter
Barrier
Volta
e
s
stem
T
pe of
round-
in
work
Groundin
resistance
200V
Class D
roundin
100
Ω
maximum
CAUTION
1. Check that the number of phases and the
rated volta
e of this product correspond
to the number of phases and volta
e of the
AC power suppl
.
Otherwise fire could occur.
2. Do not connect the AC power suppl
to the
output terminals (U, V, W).
Otherwise in
ur
could occur.
3. Do not connect a brakin
resistor directl
to
the DC terminals P(+), N(-).
Otherwise fire could occur.