2-3
Section 2 System Conguration
2-1-2 Calculation of current consumption
(1) Suppliable current
Type Internal 5V DC Internal 24V DC Externally supplied 24V DC
Main unit NA0P
oooo
-
oo
C 1000mA 400mA (Note 1) 400mA (Note 1)
Expansion unit with
power supply
NA0E24T-31 948mA 350mA 337mA
NA0E24R-34 948mA Total 337mA
Expansion power supply NA0S-2 / NA0S-4 400mA 250mA 250mA
Type Internal 5V DC Internal 24V DC
Externally supplied 24V DC
(Note 2)
Advance main unit
NA0PB14R-34C 360mA 65mA 60mA
NA0PB24R-34C 435mA 85mA 105mA
NA0PB32R-34C 520mA 110mA 138mA
NA0PB60R-34C 555mA 200mA 210mA
Basic main unit
NA0PA14T-34C 360mA 65mA 60mA
NA0PA24T-
oo
C 435mA 85mA 105mA
NA0PA32T-
oo
C 520mA 110mA 138mA
NA0PA40T-
oo
C 530mA 125mA 156mA
NA0PA60T-
oo
C 555mA 200mA 210mA
Notes:
1) When using an AC power supply type unit at a power supply voltage of 120V AC or less, the total of the internal 24V DC
and externally supplied 24V DC becomes 575mA.