Section 2 Specifications
2-8
2-3-2 Conversion characteristics of analog current input
Input range Digital output range
4 to 20 mA 0 to 16000 0 to 10000
0 to 20 mA 0 to 16000 0 to 10000
-20 to 20 mA -8000 to 8000 0 to 10000
1) Characteristic curve for the input range of 4 to 20 mA
2) Characteristic curve for the input range of 0 to 20 mA
2-3 Conversion Characteristics
Analog input current (mA)
Digital output value
(INT type)
(10250) 16400
(10000) 16000
Practicable digital
output range
(-250) -400
3.6
4
20 20.4
(Note)
Gain value
0
Offset value
Analog input current (mA)
Digital output value
(INT type)
(10250) 16400
(10000) 16000
Practicable digital
output range
-400 (-250)
-0.5
20 20.5
(Note)
Gain value
0
Offset value
Note: Parenthesized figures mean the values when the unit of digital output value is % in Fixed Range Operation mode (excl.
NP1AWH6-MR). In software Set Range Operation mode, scaling is necessary to express output values by the %.