Section 2 Specifications
2-12
2-3-4 Conversion characteristics of analog current output
Output range Digital input range
4 to 20 mA 0 to 16000 0 to 10000
0 to 20 mA 0 to 16000 0 to 10000
1) Characteristic curve for the output range of 4 to 20 mA
2) Characteristic curve for the output range of 0 to 20 mA
Note 1: Parenthesized figures mean the values when the unit of digital input value is % in Fixed Range Operation mode (excl.
NP1AWH6-MR). In Software Set Range Operation mode, scaling is necessary to express input values by the %.
Note 2: If parameter mode is activated in Software Set Range Operation mode, analog output value becomes equal to the
offset value.
2-3 Conversion Characteristics
Digital input value
(INT type)
Analog output current (mA)
20.4
20
Practicable analog
output range
(-250) -400
4
-3.6
16000
(10000)
16400
(10250)
(Note)
(Note)
Gain value
Offset value
0
Digital input value
(INT type)
Analog output current (mA)
20.5
20
Practicable analog
output range
0
16000
(10000)
16400
(10250)
(Note)
Gain value
Offset value