4-8
Section 4 Software Interface
4-1 Analog Input Module
(6) Parameter setting data register (offset address +9 to +11)
When bit 7 of the parameter type setting register (offset address +8) is set ON, module status (offset address +0) becomes
“30001” (INT type) and “parameter mode” is activated.
The set values of “operation parameter write” mode, “scaling parameter” mode or “offset/gain adjustment” mode are written in
this register.
1) When operation parameter write mode is activated
In this mode, data is set in the locations as shown below, and “operation parameter write mode flag” (bit 4 of the parameter
type setting register) is set ON.
* When using D300win, assign WORD type variables to these registers. If you access by the bit, assign a BOOL type variable
to each bit.
<Conversion enable/disable> (offset address +9)
Bit Flag name Descrip tion
0to7 Unused
8 Channel 1 Conversion enable/disable Conversion is enabled or disabled when the correspondi ng bit
is set to OFF or ON.
OF F : E nable,
ON: Disable
9 Channel 2 Conversion enable/disable
10 Channel 3 Conversi on enable/disable
11 Channel 4 Conversion enable/disable
12 Channel 5 Conversi on enable/disable
13 Channel 6 Conversi on enable/disable
14 Channel 7 Conversi on enable/disable
15 Channel 8 Conversi on enable/disable
<Input range> (offset address +10)
Bit Flag name
Descrip tion
0(L),1(H)
Channel 1 Input range Range i s set by a combination of ON/OF F status of two bits.
2(L),3(H)
Channel 2 Input range
4(L),5(H)
Channel 3 Input range
6(L),7(H)
Channel 4 Input range
8(L),9(H)
Channel 5 Input range
10 (L), 1 1 (H)
Channel 6 Input range
12 (L), 13 (H)
Channel 7 Input range
14 (L), 15 (H)
Channel 8 Input range
<NP1AXH8V-MR>
H L
OFF OFF : -10 to 10 V
OFF ON : 0 to 10 V
ON OFF : 0 to 5 V
ON ON : 1 to 5 V
<NP1AXH8I-MR>
H L
OFF OFF : 4 to 20 mA
OFF ON : 0 to 20 mA
ON OFF : -20 to 20 m
A
ON ON : 4 to 20 mA
15(F) 0
Unused (fixed to 0 (zero))
Input range
Moving average execution times
Conversion enable/disable