Section 4 Software Interface
4-1 Analog Input Module
<Procedure for scaling>
1) Set ON bit 7 of the parameter type setting register to activate parameter mode. (Make sure that module status is “30001”.)
2) Input gain and offset values to the parameter setting data register, and set ON bit 5 and bit 8 (in the case of channel 1) of
the parameter type setting register. Bit 7 must be kept ON.
(In the above example of scaling, set as follows.)
3) Make sure that bit 5 (scaling parameter write mode) and bit 8 (channel 1) of the parameter type setting register are set ON.
4) Set OFF all the bits of the parameter type setting register, and clear all the bits of the parameter setting data register to
zero. This completes the operation for adjustment.
15(F) 0
+9
+10
+11
-1000
4000