4-16
Section 4 Software Interface
4-2 Analog Output Module
4-2-2 Memory allocation in Software Set Range Operation mode
In Software Set Range Operation mode, memory allocation differs between when operating in D/A conversion mode (during
normal operation) and when operating in parameter mode.
<When operating in D/A conversion mode>
When operating in D/A conversion mode, memory allocation becomes as shown below:
Note: In D/A conversion mode, the digital input value register for channel 1 (offset address +4) serves also as the setting
command register (for changing over to parameter mode) and therefore interlock is necessary.
When a value in the range from “30000” to “32767” is input to this register, parameter mode is activated. Just after
parameter mode is activated, analog output value is equal to the offset value (0 V for the range of -10 to 10 V).
<When operating in parameter mode>
This module to CPU module
CPU module to this module
Offset
address
15(F)
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
Module status
Operation setting switch No.
Unused
Unused
Channel 1 Digital Input
Channel 2 Digital Input
Channel 3 Digital Input
Channel 4 Digital Input
Channel 5 Digital Input
Channel 6 Digital Input
Channel 7 Digital Input
Channel 8 Digital Input
0
(Note)
Up to this address
for analog 4ch modules
This module to CPU module
CPU module to this module
Offset
address
15(F)
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
Module status
Parameter type setting status
Mode changeover
Parameter type setting
0
Up to this address
for analog 4ch modules
Parameter read data
Parameter setting data
Unused
Unused
Unused
Unused