EasyManua.ls Logo

Fuji Electric MICREX-SX series - Page 51

Fuji Electric MICREX-SX series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-19
Section 4 Software Interface
4-2 Analog Output Module
(5) Parameter read data register (offset address +2 to +7)
In “operation parameter read mode”, “scaling parameter read mode” or “offset/gain adjustment mode”, the content of the
setting for the corresponding mode is stored in this register.
1) When operation parameter read mode is activated
When parameter mode is activated (when the value of the status register is “30001”) and bit 0 (zero) of the changeover
command status register is set ON, the status of the operation parameter is stored in this memory area.
* When using D300win, assign WORD type variables to these registers. If you access by the bit, assign a BOOL type variable
to each bit.
<Output range>
Bit Flag name
Descrip tion
0(L)
Channel 1 Output range
The set range is indicated by a combination of ON/OF F status of
two bits.
1(H)
2(L)
Channel 2 Output range
3(H)
4(L)
Channel 3 Output range
5(H)
6(L)
Channel 4 Output range
7(H)
8(L)
Channel 5 Output range
9(H)
10 (L)
Channel 6 Output range
11 (H)
12 (L)
Channel 7 Output range
13 (H)
14 (L)
Channel 8 Output range
15 (H)
<NP1AYH8V-MR>
H L
OFF OFF : 0 to 10 V
OFF ON : 0 to 5 V
ON OFF : 1 to 5 V
ON ON : -10 to 10 V
<NP1AYH8I-MR>
H L
OFF OFF : 4 to 20 mA
OFF ON : 0 to 20 mA
ON OFF : 4 to 20 mA
ON ON : 0 to 20 mA
2) When scaling parameter read mode is activated
When parameter mode is activated (when bit 15 of the module status register is set ON) and bit 1 (one) of the parameter type
setting status register is set ON, the current setting of the scaling parameter for the corresponding channel is displayed.
* When using D300win, assign INT type variables to these registers.
15(F) 0
+3
+2
Unused (fixed to 0 (zero))
Output range
Output enable/disable
OFF: Output enabled for all channels
ON: Output disabled for channels 5 to 8
15(F) 0
+3
+2
Offset value
Gain value

Table of Contents