4-21
Section 4 Software Interface
4-2 Analog Output Module
(7) Parameter type setting register (offset address +5)
Parameter type and channel number for reading/writing parameters are set in this register.
* When using D300win, assign a WORD type variable to this register. If you access by the bit, assign a BOOL type variable to
each bit.
Bit Flag name Description
0 Operation parameter read mode ON: Operation parameter read mode (all channels in a batch)
1 Scaling parameter read mode ON: S caling parameter read mode (indivi dual channel)
2, 3 Unused
4 Operation parameter wri te mode ON: Operation parameter write mode (all channels in a batch)
5 Scaling parameter write mode ON: Scaling parameter write mode (individual channel)
6 Offset/gain adjustment mode ON: Offset/gain adjustment mode (individual channel)
7 Unused
8 C hannel 1 In "scaling parameter read mode", " scaling parameter wri te mode" or
"offset/gain adjustment mode", arbitrary channel i s speci fied. In "scali ng
parameter read mode", one of bits 8 to 15 is set ON to indicate for whi ch
channel to set parameters. When same data is to be set in "scaling
parameter write mode" or "offset/gain adjustment mode", multiple arbitrary
channels may be specified.
9 Channel 2
10 Channel 3
11 Channel 4
12 Channel 5
13 Channel 6
14 Channel 7
15 Channel 8
15(F) 078
+5
Channel No. Parameter type