4-23
Section 4 Software Interface
4-2 Analog Output Module
<Initial value of scaling for each output range>
Output range Initial value of scaling Available range of scaling (See note.)
0 to 5 V 0 to 16000 0 to 25000
1 to 5 V 0 to 16000 0 to 25000
0 to 10 V 0 to 16000 0 to 25000
-10 to 10 V -8000 to 8000 -25000 to 25000
4 to 20 mA 0 to 16000 0 to 25000
0 to 20 mA 0 to 16000 0 to 25000
Note 1: Scaling is enabled only when the operation setting switch on the module rear panel is set to “Soft Set Range Operation
mode”. In fixed range operation mode, scaling is disabled.
Note 2: Over range is fixed to “(Gain value - Offset value) x 0.025 + Gain value”.
(“(Gain value - Offset value) x 0.0125 + Gain value” for the range of -10 to +10 V)
On the other hand, under range is fixed to “Offset value - (Gain value - Offset value) x 0.025”.
(“Offset value - (Gain value - Offset value) x 0.0125” for the range of -10 to +10 V)
Note 3: If scaling results in “resolution < maximum resolution”, digital output value does not change in steps of one.
Note 4: Once scaling values are set, they won't change even when range is changed.
<Example 1 of scaling>
<Example 2 of scaling>
Digital input
value
(INT type)
Analog output voltage (V)
10.25
10
-10
-10.25
0
8000 8200
-8200 -8000
Gain value
Offset value
Digital input
value
(INT type)
Analog output voltage (V)
10.25
10
-10
-10.25
4000 4200
-4200 -4000
Gain value
Offset value
Gain: 4000
Offset: -4000
Set values
0
Digital input
value
(INT type)
Analog output current (mA)
20.4
20
4
-3.6
-400
16000 16400
Gain value
Offset value
Gain: 4000
Offset: 1000
Set values
0
0
Digital input
value
(INT type)
Analog output current (mA)
20.4
20
4
1000
4000 4075
Gain value
Offset value
-3.6

Table of Contents