App.1-9
Appendix 1 Offset/Gain Adjustment <D300win>
Appendix 1-2 Offset/Gain Adjustment of Analog Output Module
5) After the completion of offset adjustment, set ON bit 0 (zero) of the parameter setting data register (offset address +6) to
write the offset adjustment value in the module internal EEPROM. When bit 0 (zero) of offset address +2 is set ON, the
writing of EEPROM is completed. After confirming this, set OFF bit 0 (zero) of the parameter setting data register.
6) Then set bit 15 ON of the parameter setting data register (offset address +6) and, in the same way as offset adjustment,
adjust output value by setting ON and OFF bit 8 (output value Down) and bit 9 (output value Up). (Gain adjustment)
0: Offset value adjustment
Output value Up
Output value Down
* While the output value up bit and down bit are on, the values change. (1% per 2minutes)
Completion of EEPROM writing
EEPROM write command