App.2-7
Appendix 2 Offset/Gain Adjustment <SX-Programmer Standard>
Appendix 2-2 Offset/Gain Adjustment of Analog Output Module
<Offset/gain adjustment with SX Control Utility of D300win>
2) Offset is adjusted first.
Input a value in the range from "30000" to "32767" to offset address +4 to change mode.
Make sure that bit 15 of the module status register
(offset address +0) is set ON (parameter mode).
1) Connect a loader to a PLC online to monitor the input/output areas of the analog input module that is to be adjusted.
Input/output status of analog output
module (of 8ch specification)
3) Set ON bit 6 of the parameter type setting register (offset address +5) to activate offset/gain adjustment mode, and set ON
the bit for the channel that is to be adjusted (the corresponding one of bits 8 to 15 of the parameter type setting register).
Channel 8 Channel 7 Channel 6 Channel 5 Channel 4 Channel 3 Channel 2 Channel 1