71
3rd block parameter
FLo1
MV1 during FALT (146)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to specify the control output value when the controller falls into FALT (input error).
Setting range
-5.0 to 105.0%
[Setting example] Setting the OUT1 during FALT to 5% –––––––––––––––––––––
Display Operating procedure
1.
Press and hold the key for about ve seconds during the SV/PV display.
appears.
2.
Press the key to display .
3.
Press the key.
The setpoint starts blinking.
4.
Press the , or keys to change “ -5.0 ” to “ 5.0 .”
5.
Press the key or wait for three seconds to save the change.
6.
Press the key.
The screen returns to the SV/PV display.